USD USD: TRY
EUR EUR: TRY
GBP GBP: TRY

D2030M Intrinsically Safe Digital Multiplexer

Key Features

  • 🔹 Intrinsically Safe For Zone 1, 2 – Gas Group IIC, IIB, IIA T4
  • 🔹 Inputs From Contacts Or EN60947-5-6 Proximity Detectors
  • 🔹 Expandable Up To 3968 Channels Over Modbus Network
  • 🔹 EMC Compatibility: EN61000-6-2, EN61000-6-4
  • 🔹 High Density – 32 Channels Per Unit, 128 Per System
  • 🔹 Configurable With Free PC Software (SWC2090)
  • 🔹 Saves Cost On PLC/DCS I/O Cards – Modbus Output
  • 🔹 One Terminal Block Per Input – No External Block Required
🟢 Active
32 Channels – Product Lifecycle Policy

Certifications

TypeDescriptionAreaNumberIssued byIssue Date
ATEXDEKRA ATEX D2000 System English Certificate ( EN )EuropeBVS 06 ATEX E 101 XEXAM2018-05-29
EMCD2000 EAC EMC Declaration of Conformity ( RU )Eurasian CommunityЕАЭС N RU Д-IT.НХ37.В.06310/20EUROCERT2020-08-13
ExD2000 CCC certificate for China ( EN )China2020322316000820NEPSI2023-04-30
ExEAC Ex Certificate for D2000 Series ( RU )Eurasian CommunityЕАЭС RU С-IT.НА67.В.00106/20TECHNOPROGRESS2020-08-21
ExFM No.3024643-3029921C Certificate ( EN )North America3024643-3029921CFM2005-12-16
IECExDEKRA IECEx for D2000 Series ( EN )InternationalIECEx BVS 09.0049XDEKRA2013-11-29
MetrologicalMetrological Certificate Russia for D2000 Series ( RU )Russia46390-11ROSSTANDART2021-03-10

Connections

Description

Supply
VoltageVia D2050M gateway unit.
Max. Power Consumption200 mW.
Input
Switching Current LevelsON ≥ 2.1 mA, OFF ≤ 1.2 mA, switch current ≈ 1.65 mA ± 0.2 mA hysteresis.
Fault Current LevelsOpen fault ≤ 0.2 mA, short fault ≥ 6.0 mA.
Fault DetectionEnabled or disabled, programmable independently for each channel.
Input Equivalent Source7.5 V 1 KΩ typical (7.5 V no load, 7.5 mA short circuit).
Input Channels32.
Excitation TimeProgrammable from 1 ms to 35 ms independently for each channel.
Scan Cycle Time50 ms for four D2030M units (128 channels) at minimum sensor excitation time or the sum of each channel scan time, whichever is greater.
Isolation
Test VoltageI.S. In/Supply-Communication line 500 V; I.S. In/Ground 500 V; I.S. In/I.S. In between units 500 V; Communication line/Ground 500 V.
Environmental Conditions
OperatingTemperature limits –40 to +60 °C, relative humidity max 90 % non-condensing, up to 35 °C.
StorageTemperature limits –45 to +80 °C.
Safety Description
Safety ParametersUo/Voc = 10.7 V, Io/Isc = 14 mA, Po/Po = 38 mW at terminals 1-2, 3-4 of channel 1 to 32. -40 °C ≤ Ta ≤ 60 °C.
Mounting
TypeT35 DIN Rail according to EN50022.
WeightAbout 680 g.
ConnectionBy polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
LocationSafe Area/Non Hazardous Locations or Zone 1, 2, Group IIC, IIB, IIA T4, Class I, Division 1, Groups A, B, C, D Temperature Code T4 and Class I, Zone 1, 2, Group IIC, IIB, IIA T4 installation.
Protection ClassIP 20.
DimensionsWidth 127 mm, Length 220 mm, Depth 78 mm.

Additional information

GMI-Status

Active

GMI-Channels

32 N.

Multiplexer Systems

Intrinsically Safe Multiplexer System

GMI-Temperature

-40…+60 °C

Max Load Voltage

24 Vdc