D2011M Intrinsically Safe Temperature Multiplexer

Key Features

  • 🔹 Intrinsically Safe For Zone 1, 2, Class I/Div 1,2, Group IIC, IIA, IIB
  • 🔹 Universal Inputs: mV, Thermocouples, RTD From Zone 0, 1, 2
  • 🔹 200 V / 60 V / 500 V Isolation For Safe Sensor Grounding
  • 🔹 Expandable Up To 7936 Channels Over Modbus
  • 🔹 Redundant Field Communication/Supply Lines
  • 🔹 18-Bit High Accuracy A/D Converter
  • 🔹 16 Channels Per Unit – 256 Channels Per System
  • 🔹 Easy Configuration via D2050M Gateway & Free SWC2090 Software
  • 🔹 Cost-Effective – Reduces PLC/DCS I/O Card Requirements
🟢 Active
16 Channels – Product Lifecycle Policy

Description

Supply
VoltageVia D2010M multiplexer unit.
Max. Power Consumption10 mW.
Input
TypeMillivolt or thermocouple type A1, A2, A3, B, E, J, K, L DIN, L GOST, N, R, S, S GOST, T, U or 3-4 wires RTD Pt100, Pt200, Pt300 to DIN43760, Pt100 (0.3916), Ni 100 or Pt100, Pt50, Cu100, Cu53, Cu50, Cu 46 (GOST) or mA signals with external shunt (D1090Q) or V signals with external divider (D1094Q).
Input Channels16 for mV, RTD or TC without automatic reference junction compensator or 15 using automatic reference junction compensator for thermocouples inputs (channel 16 is used for compensator connection).
Resolution2 μV on mV or thermocouple, 10 mΩ on RTD.
Input RangeWithin sensor’s rated limits; mV range from -21 to +80 mV or -21 to +21 mV, resistance range from 0.0 to 400.0 Ω.
Measuring RTD Current≤ 200 μA.
RTD Line Resistance Compensation≤ 10 Ω.
Thermocouple Reference Junction CompensationAutomatic with external sensor on channel nr. 16 (OPT2091 separately ordered or user selectable RTD) or fixed programmable from -60 to +100 °C.
BurnoutUp, down or disabled.
Performance
TypeField units powered by D2010M multiplexer at 23 ± 1 °C ambient temperature.
Calibration and Linearity Accuracy≤ ±20 μV on mV or thermocouple, 200 mΩ on RTD or ±0.05 % of input value, whichever is greater.
Temperature Influence≤ ±2 μV, 10 mΩ or ±0.01 % of input value for a 1 °C change.
Reference Junction Compensation Influence≤ ±1 °C (thermocouple sensors only).
Isolation
Test VoltageI.S. In/I.S. In 200 V for mV/TC, 60 V for RTD; I.S. In/Ground 500 V.
Environmental Conditions
OperatingTemperature limits –40 to +60 °C, relative humidity max 90 % non-condensing, up to 35 °C.
StorageTemperature limits –45 to +80 °C.
Safety Description
Safety ParametersUo/Voc = 10.7 V, Io/Isc = 7 mA, Po/Po = 19 mW at terminals 1-2-3-4 of channel 1 to 16. -40 °C ≤ Ta ≤ 60 °C.
Mounting
TypeT35 DIN Rail according to EN50022.
WeightAbout 640 g.
ConnectionBy polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
LocationSafe Area/Non Hazardous Locations or Zone 1, 2, Group IIC, IIB, IIA T4, Class I, Division 1, Groups A, B, C, D Temperature Code T4 and Class I, Zone 1, 2, Group IIC, IIB, IIA T4 installation.
Protection ClassIP 20.
DimensionsWidth 127 mm, Length 220 mm, Depth 78 mm.

Additional information

GMI-Status

Active

GMI-Channels

16 N.

Multiplexer Systems

Intrinsically Safe Multiplexer System

GMI-Temperature

-40…+60 °C