| Supply |
|---|
| Voltage | 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
| Current Consumption @ 24 V | 260 mA with four multiplexer unit connected typical. |
| Power Dissipation | 5.0 W with 24 V supply voltage and four multiplexer unit connected. |
| Max. Power Consumption | At 30 V supply and output short circuit condition 8.5 W. |
| Input/Output I.S. Hazardous Area |
|---|
| Type | Dual serial communication line, proprietary protocol and power to supply field multiplexer unit D2010M or D2030M (up to four). |
| Scan Cycle Time | 50 ms for a system with 4 D2030M unit (128 digital channel), 1700 ms for a system with 4 D2010M and 12 D2011M (256 analog channel). |
| Output/Input Safe Area |
|---|
| Type | Modbus RTU protocol up to 115.2 Kbit/s with RS-485 redundant connection. |
| Terminating Impedance | 250 Ω DIP-switch selectable. |
| Transmission Speed | 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 Kbit/s. |
| Transmission Cable Length | ≤ 1200 m up to 93.75 Kbit/s, ≤ 1000 m up to 115.2 Kbit/s. |
| Configuration Line |
|---|
| Type | RS232 connection (EIA RS232-C applicable standard). |
| Transmission Speed | 19.2 Kbit/s. |
| Transmission Cable Length | ≤ 15 m. |
| Connection | SUB D 9 poles male connector (requires female mating connector). |
| Isolation |
|---|
| Test Voltage | I.S. Out/RS-232 Configuration Line 1.5 KV; I.S. Out/RS-485 Modbus Line 1.5 KV; I.S. Out/Supply 1.5 KV; RS-232 Configuration Line/Supply 500 V; RS-485 Modbus Line/Supply 500 V; RS-232 Configuration Line/RS-485 Modbus Line 500 V. |
| Environmental Conditions |
|---|
| Operating | Temperature limits –40 to +60 °C, relative humidity max 90 % non-condensing, up to 35 °C. |
| Storage | Temperature limits –45 to +80 °C. |
| Safety Description |
|---|
| Safety Parameters | Um = 250 Vrms, -40 °C ≤ Ta ≤ 60 °C. |
| Mounting |
|---|
| Type | T35 DIN Rail according to EN50022. |
| Weight | About 570 g. |
| Connection | By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm². |
| Location | Safe Area/Non Hazardous Locations installation. |
| Protection Class | IP 20. |
| Dimensions | Width 127 mm, Length 220 mm, Depth 78 mm. |