D1054S SIL 2 Repeater Power Supply & Trip Amplifiers

Ürün Özellikleri

  • 🔹 SIL2 / SC2 Uyumlu
  • 🔹 Zone 0 (Zone 20), Division 1 Giriş – Zone 2, Division 2 Kurulum
  • 🔹 4-20 mA Loop veya 0/4-20 mA Harici Güçlü Giriş Sinyali
  • 🔹 0/4-20 mA, 0/1-5 V, 0/2-10 V Çıkış – Lineer veya Ters
  • 🔹 Geniş Bant HART® Uyumlu Akıllı İletişim
  • 🔹 Giriş ve Çıkış Kısa Devre Koruması
  • 🔹 İki Bağımsız Trip Rölesi
  • 🔹 Arıza Tespiti için Çıkış (Burnout Detection)
  • 🔹 Yüksek Hassasiyet – Mikroişlemci Kontrollü A/D Dönüştürücü
  • 🔹 3 Port İzolasyon: Giriş / Çıkış / Besleme
  • 🔹 EMC Uyumu: EN61000-6-2, EN61000-6-4, EN61326-1
  • 🔹 Tam Programlanabilir Çalışma Parametreleri
  • 🔹 Maks. 250 Vrms (Um) İzin Verilen Gerilim
🔍 Discover D1000
🟡 SPARE-ONLY
Sonraki Aşama: OBSOLETE (31.12.2025)

Description

TypeDescription
Supply Type12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp
Supply Current Consumption90 mA with 20 mA input/output and relays energized
Supply Power Dissipation1.7 W with 24 V supply, 20 mA input/output and relays energized.
Supply Max. power consumptionat 30 V supply voltage, input short circuit, overload condition, relays energized and PPC1090 connected, 2.9 W.
Input Type0/4 to 20 mA (separately powered input, voltage drop ≤ 1 V) or 4 to 20 mA (2 wire Tx current limited at ≈ 25 mA).
Input Integration time100 ms
Input Resolution1 µA.
Input Input range0 to +22 mA
Transmitter line voltage Type≥ 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 40 KHz frequency band.
Burnout Typeenabled or disabled. Analog output can be programmed to detect burnout condition with downscale or highscale forcing. Alarms can be programmed to detect burnout condition.
Burnout Rangelow and high separated trip point value programmable between -5 to +25 mA.
Output Type0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V.
Output Resolution1 µA current output or 1 mV voltage output.
Output Transfer characteristiclinear or reverse.
Output Response time≤ 50 ms (10 to 90 % step change).
Output Output ripple≤ 20 mVrms on 250 Ω communication load on 0.5 to 40 KHz band.
Output Frequency response0.5 to 40 KHz bidirectional within 3 dB (HART® and higher frequency protocols) only with mA direct current output.
Alarm Trip point rangewithin rated limits of input sensor (see input for step resolution).
Alarm ON-OFF delay time0 to 1000 s, 100 ms step, separate setting.
Alarm Hysteresis0 to 5 mA (see input for step resolution).
Alarm Outputvoltage free SPST relay contact.
Alarm Contact rating2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load).
Performance TypeRef. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Performance InputCalibration and linearity accuracy: ≤ ± 20 μA Temperature influence: ≤ ± 1 μA of input for a 1 °C change.
Performance Analog OutputCalibration accuracy: ≤ ± 0.1 % of full scale. Output Linearity error: ≤ ± 0.05 % of full scale. Supply voltage influence: ≤ ± 0.05% of full scale for min to max supply change Load influence: ≤ ± 0.05% of full scale for 0 to 100 % load resistance change Temperature influence: ≤ ± 0.01 % on zero and span for a 1 °C change.
Isolation Test VoltageI.S. In/Outs 1.5 KV; I.S. In/Supply 1.5 KV; Analog Out/Supply 500 V; Analog Out/Alarm Outs 1.5 KV; Alarm Outs/Supply 1.5 KV; Alarm Out/Alarm Out 1.5 KV.
Environmental conditions Operatingtemperature limits -20 to + 60 °C, relative humidity max 95 %.
Environmental conditions Storagetemperature limits – 45 to + 80 °C.
Safety description Safety parametersUo/Voc = 26.3 V, Io/Isc = 91 mA, Po/Po = 597 mW at terminals 14-15. Uo/Voc = 1.1 V, Io/Isc = 56 mA, Po/Po = 16 mW at terminals 15-16. Ui/Vmax = 30 V, Ii/Imax = 128 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C.
Mounting TypeEN/IEC60715 TH 35 DIN-Rail.
Mounting Weightabout 175 g.
Mounting Connectionby polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Mounting LocationSafe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Mounting Protection classIP 20.
Mounting DimensionsWidth 22.5 mm, Depth 99 mm, Height 114.5 mm.

Additional information

GMI-Applications

Analog Input

SIL Seviyesi

SIL 2