| Control Input Type | switch contact, logic level reverse polarity protected. |
| Control Input Trip Voltage | OFF ≤ 5.0 V, ON ≥ 20.0 V (max 30 V). |
| Control Input Current | 5 mA @ 24 V. |
| Override Input Type | override control signal de-energizes output when enabled by dip-switch. |
| Override Input Range | 24 Vdc nom (20 to 30 Vdc) to disable; 0 to 5 Vdc to de-energize, reverse polarity protected. |
| Override Input Current | 5 mA @ 24 V. |
| Output Type | 45 mA at 13.0 V (Out A), 10.2 V (Out B), 8.5 V (Out C). |
| Short Circuit Current | ≥ 50 mA (55 mA typical). |
| Response Time | ≤ 10 ms. |
| Frequency Response | 50 Hz. |
| Fault Detection Type | open/short circuit detection with dip-switch; output de-energized until fault is cleared. |
| Short Output Detection | load ≤ 50 Ω (≈ 2 mA forcing). |
| Open Output Detection | load > 10 KΩ. |
| Fault Signalling Type | voltage free NE SPST optocoupled open-collector transistor. |
| Open-Collector Rating | 100 mA at 35 Vdc (≤ 1.5 V drop). |
| Leakage Current | ≤ 50 µA at 35 Vdc. |
| Fault Response Time | ≤ 5 ms. |
| Isolation Test Voltage | I.S. Out/In/Fault/Override 1.5 KV; others 500 V. |
| Operating Conditions | -20 to + 60 °C, RH max 90 %, non condensing. |
| Storage Conditions | -45 to + 80 °C. |
| Safety Parameters | Uo/Voc = 24.8 V, Io/Isc = 147/108/93 mA (Out A/B/C), Po/Po = 907/667/571 mW. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
| Mounting | EN/IEC60715 TH 35 DIN-Rail. |
| Weight | about 135 g. |
| Connection | by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |