D1045Y Bus Powered Safe Isolator

Ürün Özellikleri

  • 🔹 Zone 0 (Zone 20), Division 1 Giriş – Zone 2, Division 2 Kurulum
  • 🔹 İzole Komutlu Gerilim Girişi
  • 🔹 Loop Powered veya Bus Powered Kullanım
  • 🔹 1 veya 2 Pozisyonlu Yön Valflerini Sürmek İçin Uygun
  • 🔹 Çıkış Kısa Devre Korumalı ve Akım Sınırlamalı
  • 🔹 Üç Port İzolasyonu: Giriş / Çıkış / Besleme
  • 🔹 EMC Uyumluluğu: EN61000-6-2, EN61000-6-4
  • 🔹 Maks. 250 Vrms (Um) İzin Verilen Gerilim
🟡 PHASE-OUT
Yedek Parça Desteği: 01.01.2027’ye Kadar

Description

TypeDescription
Output Module Voltage24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
Output Module Current Consumption90 mA @24 V with output energized at nominal load, 110 mA @24 V with short circuit output.
Output Module Power Dissipation1.4 W with 24 V supply voltage, output energized at nominal load.
Output Module Max. Power Consumptionat 30 V supply voltage and short circuit output, 2.9 W
Output Module Input Typeswitch contact, logic level or loop powered.
Output Module Trip Voltage LevelsOFF status ≤ 1.0 V, ON status ≥ 6.0 V (maximum 30 V)
Output Module Input Current Consumption3 mA @24 V(≈ 10 KΩ input impedance).
Output Module Output Type70 mA at 11.3 V (Out A), 70 mA at 12.2 V (Out B)
Output Module Short Circuit Current≥ 85 mA (90 mA typical)
Output Module Response Time20 ms (power up in 600 ms typical in loop powered mode).
Output Module Test VoltageI.S. Out/In 1.5 KV; I.S. Out/Supply 1.5 KV; In/Supply 500 V; In/In 500 V
Output Module Operating Conditions-20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C.
Output Module Storage Conditions– 45 to + 80 °C.
Output Module Safety ParametersUo/Voc = 18.9 V, Io/Isc = 249 mA, Po/Po = 1173 mW (Out A), 1286 mW (Out B). Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.
Output Module MountingEN/IEC60715 TH 35 DIN-Rail.
Output Module Weightabout 130 g.
Output Module Connectionby polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Output Module LocationSafe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Output Module Protection ClassIP 20.
Output Module DimensionsWidth 22.5 mm, Depth 99 mm, Height 114.5 mm.

Additional information

GMI-Applications

Digital Output

SIL Seviyesi

SIL 2