| Supply |
|---|
| Type | 24 Vdc nom (18 to 30 Vdc), reverse polarity protected. |
| Current Consumption | 45 mA @ 24 Vdc (no fault), typical. |
| Power Dissipation | 1.1 W @ 24 Vdc (no fault), typical. |
| Input |
|---|
| Type | 24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes. |
| Current Consumption | 40 mA @ 24 Vdc (no fault), typical. |
| Power Dissipation | 1.0 W @ 24 Vdc (no fault), typical. |
| Output |
|---|
| Type | Voltage free 2+2 SPST relay contact (2 paralleled contacts in series) at terminals 13-15 and 14-16, close when relay energized, open in de-energized condition. |
| Contact Material | Ag Alloy (Cd free), gold plated. |
| Contact Rating | 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load). |
| Contact Min. Switching Current | 1 mA. |
| Contact Inrush Current | 6 A @ 24 Vdc, 250 Vac. |
| DC and AC Load Breaking Capacity | Refer to Instruction Manual. |
| Contact Current Derating | Refer to Instruction Manual. |
| Mechanical / Electrical Life | 5 × 10⁶ / 3 × 10⁴ operations, typical. |
| Operate / Release Time | 30 ms / 30 ms, typical. |
| Fault |
|---|
| Type | Load & line short/open circuit, supply voltage and earth leakage monitor. |
| Diagnostics Equivalent Source | When the load is off, the diagnostic circuit forces a sensing signal: 5.5 V open circuit, 10 mA short circuit, typical. |
| Line + Load Resistance | Programmable up to 50 kΩ. |
| Load Current | Programmable up to 5 A. |
| Load Supply Voltage | Programmable up to 250 Vdc/Vac. |
| Load Earth Leakage | Programmable up to 3 MΩ. |
| Fault Signaling | Voltage free DPST contact. |
| Fault 1 Rating | 0.5 A 30 Vac 15 VA, 0.5 A 50 Vdc 25 W (resistive load). |
| Fault 2 Rating | 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load). |
| Response Time | 4 s, typical. |
| Modbus Interface |
|---|
| Type | Modbus RTU RS-485 up to 115.2 kbps for monitor/configuration/control. |
| Isolation |
|---|
| Test Voltage | Output/Input 2.5 kV; Output/Supply 2.5 kV; Output/Fault Outputs 2.5 kV; Output/RS485 Modbus 2.5 kV; Input/Supply 500 V; Input/Fault Output 1 500 V; Input/Fault Output 2 2.5 kV; Input/RS485 Modbus 500 V; Supply/Fault Output 1 500 V; Supply/Fault Output 2 2.5 kV; Supply/RS485 Modbus 500 V. |
| Environmental Conditions |
|---|
| Operating Temperature | –40 to +70 °C. |
| Storage Temperature | –45 to +80 °C. |
| Mounting |
|---|
| Type | DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. |
| Weight | About 195 g. |
| Connection | By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
| Dimensions | Width 22.5 mm, Depth 123 mm, Height 120 mm. |