USD USD: TRY
EUR EUR: TRY
GBP GBP: TRY

D5098S SIL3 Relay Out Module 5 A NE Loads

Key Features

  • 🔹 SIL 3 / SC 3 For NE/ND Loads With ND/NE Driver
  • 🔹 Installation In Zone 2
  • 🔹 Up To 5 A Functional / 6 A Inrush Current
  • 🔹 Low Input Voltage
  • 🔹 Load Disconnection On Both Supply Lines Available
  • 🔹 High Process Availability To Avoid Spurious Trips
  • 🔹 Compatible With DCS/PLC Pulse Testing
  • 🔹 Line & Load Short/Open Circuit Detection
  • 🔹 Load Voltage Monitoring
  • 🔹 Field Fault Mirroring To The PLC DO
  • 🔹 Service Contact Available
  • 🔹 Input / Output / Supply Isolation
🟢 Active
🔢 Channels: 1
Product Lifecycle Policy: Details

Connections

Dimensions

Certifications

TypeDescriptionAreaNumberIssued byIssue Date
ATEXIMQ ATEX D5098 Series English Certificate ( EN )EuropeIMQ 17 ATEX 009 XIMQ2022-05-03
EMCD5000/D6000 EAC EMC Declaration of Conformity ( RU )Eurasian CommunityЕАЭС N RU Д-IT.PA08.B.82326/24CONTROL2024-09-26
ExD5000 CCC certificate for China ( EN )China2020322316000978NEPSI2024-03-22
ExEAC Ex Certificate for D5000 Series ( RU )Eurasian CommunityЕАЭС RU С-IT.AA87.В.01310/24CCVE2024-06-13
ExEmirates Certificate of Conformity D5098 series ( EN )United Arab Emirates24-10-127922/E24-10-132495/NB0002SGS2024-10-22
FSMTUV IT 22 SIL 0093 Functional Safety Certificate ( EN )InternationalTUV IT 22 SIL 0093TUV_SUD2022-07-25
IECExIMQ IECEx D5098 Series Certificate ( EN )InternationalIECEx IMQ 17.0006XIMQ2022-05-03
MaritimeKR Maritime Certificate D5000 Series ( EN )InternationalMIL20769-EL002KR2024-06-26
MaritimeDNV Maritime Certificate TAA00001U0 for D5000 series for website ( EN )InternationalTAA00001U0DNV-GL2024-04-02
SILTUV C-IS-272994-01 SIL Certificate Summary ( EN )InternationalC-IS-272994-01TUV_SUD2022-10-14

Description

Input
Type24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes.
Current Consumption45 mA @ 24 Vdc, typical
Power Dissipation1.1 W (D5098D), @ 24 Vdc, typical.
Output
Type1 voltage free SPDT relay contact identified with outputs: Out 1 (NO contact) terminals 7-8 and Service Load Out 1 (NC contact) terminals 7-11; 1 voltage free SPDT relay contact identified with outputs Out 2 (NO contact) terminals 9-10 and Service Load Out 2 (NC contact) terminals 9-12 (only for D5098D). Terminals 7-8 (Out 1) and 9-10 (Out 2, only for D5098D) are open when relay is de-energized, closed in energized relay condition. Service load outputs (not SIL) at terminals 7-11 and 9-12 (only for D5098D) are normally closed when relay is de-energized, open in energized relay condition.
Contact MaterialAg Alloy (Cd free), gold plated.
Contact Rating5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load).
Contact Min. Switching Current1 mA.
Contact Inrush Current6 A @ 24 Vdc, 250 Vac.
DC and AC Load Breaking CapacityRefer to Instruction Manual.
Contact Current DeratingRefer to Instruction Manual.
Mechanical / Electrical Life5 × 10⁶ / 3 × 10⁴ operations, typical.
Operate / Release Time30 ms / 20 ms, typical.
Isolation
Test VoltageOutput/Input 1.5 kV; Input/Input 500 V; Output/Output 1.5 kV.
Environmental Conditions
Operating Temperature–40 to +70 °C.
Storage Temperature–45 to +80 °C.
Mounting
TypeDIN-Rail 35 mm, or on custom Term. Board.
WeightAbout 110 g
ConnectionBy polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
DimensionsWidth 12.5 mm, Depth 123 mm, Height 120 mm.

Additional information

GMI-Status

Active

GMI-Series

D5000

GMI-Channels

1 N

SIL Seviyesi

SIL 3

GMI-Input-Range

24 Vdc

GMI-Output Type

1 Voltage Free SPDT

LOAD STATUS

NE / Energize To Trip

Max Contact Rating

5 A

Max Load Voltage

250 Vdc

Safety Relay In

Relay Output

GMI-Temperature

-40…+70 °C