| Supply Voltage | 24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
| Current Consumption @ 24 V | 110 mA with 80 mA nominal load, 130 mA with 100 mA load and 150 mA with short circuit output. |
| Power Dissipation | 1.8 W with 24 V supply voltage and 100 mA nominal load. |
| Max. Power Consumption | at 30 V supply voltage and short circuit output, 3.9 W. |
| Isolation Test Voltage | I.S. Out/Supply 1.5 KV. |
| Output Type | 100 mA at 13.5 V (20.5 V no load, 68.3 Ω series resistance). |
| Short Circuit Current | ≥ 115 mA. |
| Operating Conditions | Temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. |
| Storage Conditions | Temperature limits – 45 to + 80 °C. |
| Safety Parameters | Uo/Voc = 23.6 V, Io/Isc = 352.8 mA, Po/Po = 1674 mW at terminals 13/15-14/16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
| Mounting Type | EN/IEC60715 TH 35 DIN-Rail. |
| Weight | About 110 g. |
| Connection | By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm². |
| Location | Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
| Protection Class | IP 20. |
| Dimensions | Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |