| General |
| Power Dissipation |
0.55 W (passive Tx), 1.05 W (active Tx) @ 24 Vdc with 20 mA, 24 Vdc + 250 Ω output, typical. |
| System Supply |
| Voltage |
24 Vdc nom (18 to 30 Vdc). |
| Current Consumption |
23 mA @ 24 Vdc with 20 mA, typical. |
| System Out |
| Type |
Current 4 to 20 mA. The module always sinks current and the Termination Board extends its use to source loops. |
| Response Time |
≤ 20 ms (4 to 20 mA or 20 to 4 mA). |
| Current Limitation |
26 mA typical. |
| Maximum Load |
600 Ω. |
| Maximum Voltage |
30 V. |
| Minimum Voltage |
15 V (including series resistance voltage drop). |
| Field In |
| Type |
Current 4 to 20 mA, passive or active Tx. |
| Passive Tx Line Voltage |
20 V minimum @ 20 mA. |
| Active Tx Voltage Drop |
6.5 V maximum @ 20 mA. |
| Current Limitation |
26 mA typical. |
| Fault |
| Type |
An out-of-range fault with configurable limits is available on the common fault line. |
| Performance |
| Ref. Conditions |
24 V supply, 24 V + 250 Ω output, 23 ± 1 °C ambient temperature. |
| Linearity Accuracy |
≤ ± 20 µA. |
| Calibration Accuracy |
≤ ± 20 µA. |
| Temp. Influence |
≤ ± 2 µA/°C. |
| Isolation |
| Test Voltage |
Field In/System Out 2.5 kV; Field In/System Supply 2.5 kV; System Out/System Supply 500 V. |
| Environmental Conditions |
| Operating Temperature |
–40 to +70 °C. |
| Storage Temperature |
–45 to +80 °C. |
| Mounting |
| Type |
On custom Termination Board. |
| Weight |
About 55 g. |
| Dimensions |
Width 10 mm, Depth 80 mm, Height 120 mm. |