X1-IS-UNI-01-S SIL2 Intrinsically Safe Isolator

Key Features

  • 🔹 SIL 3/2 Depending On Applications / SC 3
  • 🔹 Input From Zone 0 / Division 1
  • 🔹 Installation In Zone 2 / Division 2
  • 🔹 Loop Disconnection To Ease Maintenance Operations
  • 🔹 Suitable For AI, AO, DI And DO Applications Without Configuration
  • 🔹 HART® Compatible (Passive And Active AI/AO Loops)
  • 🔹 Line & Load Short/Open Circuit Programmable Diagnostics
  • 🔹 Out-Of-Range Fault With Programmable Thresholds
  • 🔹 Digital Calibration Available Through Configuration Software
  • 🔹 Input And Output Short Circuit Proof
  • 🔹 Field Fault Mirroring To The DCS/PLC UNI Card
  • 🔹 High Accuracy
  • 🔹 Three-Port Isolation, Input/Output/Supply
🟢 Active
Discover Universal – Product Lifecycle Policy

Description

General
AI Power Dissipation0.90 W (passive Tx), 1.05 W (active Tx) with 20 mA, 24 V + 250 Ω @ 24 Vdc, typical.
AO Power Dissipation0.75 W with 20 mA on I/P out @ 24 Vdc, typical.
DI Power Dissipation0.95 W with short circuit input @ 24 Vdc, typical.
DO Power Dissipation1.60 W with 40 mA, 1.40 with 35 mA @ 24 Vdc, typical.
System Supply
Voltage24 Vdc nom (18 to 30 Vdc).
AI Current Consumption32 mA (passive Tx), 18 mA (active Tx) with 20 mA @ 24 Vdc, typical.
AO Current Consumption30 mA with 20 mA on I/P out @ 24 Vdc, typical.
DI Current Consumption30 mA with short circuit input @ 24 Vdc, typical.
DO Current Consumption67 mA with 40 mA @ 24 Vdc, typical.
System In/Out
TypeCurrent 0 to 40 mA, mirrored from Field. Module always sinks current; Termination Board extends use to source loops.
Response Time5 ms.
Maximum Load600 Ω (AI usage).
Minimum Voltage15 V (AI, DI, DO usage).
Maximum Voltage30 V (all applications).
Field In/Out
TypeField interface specs depend on terminals and usage.
Current Limitation45 mA, typical, for all applications.
AICurrent 4 to 20 mA, passive or active Tx + HART.
AI Passive Tx Line Voltage15.5 V minimum @ 20 mA.
AI Active Tx Voltage Drop6.5 V maximum @ 20 mA.
AOCurrent 4 to 20 mA + HART.
AO Maximum Load600 Ω.
DI8 V / 1 kΩ typical, according to NAMUR standard.
DO0 to 40 mA, linear derating from 40 mA (60 °C) to 35 mA (70 °C).
DO Output Voltage8.5 V minimum @ 40 mA.
Fault
TypeLoad short/open with settable limits on voltage, current and resistance.
Fault SignallingCommon fault & fault mirroring on DCS/PLC IO.
Performance
Reference Conditions24 V supply, 250 Ω load, 23 ± 1 °C Tamb.
Calibration Accuracy≤ ± 20 µA.
Linearity Accuracy≤ ± 20 µA (4 to 20 mA), ± 60 µA (0 to 40 mA).
Temperature Influence≤ ± 2 µA/°C.
Isolation
TypeField In/Out to System In/Out 2.5 kV; Field In/Out to System Supply 2.5 kV; System In/Out to System Supply 500 V.
Environmental Conditions
Operating Temperature–40 to +70 °C.
Storage Temperature–45 to +80 °C.
Safety Description
EquipmentAssociated apparatus and non-sparking electrical equipment.
Safety ParametersUo = 26.7 V, Io = 92 mA, Po = 610 mW @ terminals A-Z
Uo = 10.7 V, Io = 11 mA, Po = 29 mW @ terminals C-Z
Uo = 1.1 V, Io = 56 mA, Po = 16 mW @ terminals B-Z
Ui = 30 V, Ii = 120 mA, Ci = 0.6 nF, Li = 0 µH @ terminals B-Z
Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.
Mounting
TypeOn custom Termination Board.
WeightAbout 50 g.
DimensionsWidth 10 mm, Depth 80 mm, Height 120 mm.

Additional information

GMI-Applications

Universal

GMI-Status

Active

SIL Seviyesi

SIL 2

GMI-Temperature

-40…+70 °C