Description
Supply | |
---|---|
Nominal System Voltage (Un) | 24 V DC |
Max Continuous Operating Voltage (Uc) | 30 V DC |
Rated Current | 600 mA (40°C) |
Protection | |
IEC Test Classification | C1 / C2 / C3 / D1 |
Protection of Signal Types | 0/4-20 mA HART, Digital I/O, World FIP, F&G |
Nominal Discharge Current (In) | (8/20) μs: 5 kA (core-core) / 5 kA (core-ground) / 5 kA (core-earth) |
Impulse Discharge Current (Iimp) | (10/350) μs: 0.5 kA (core-core) / 0.5 kA (core-ground) / 0.5 kA (core-earth) |
Total Discharge Current (Itotal) | (8/20) μs: 10 kA |
Max. Total Discharge Current (Imax) | (8/20) μs: 20 kA (for one time) |
Series Resistance | 1.65Ω ± 20% |
Voltage Protection Level (Up) | ≤ 150 V (C1 – 1 kV/500 A) core-core ≤ 275 V (C2 – 10 kV/5 kA) core-core ≤ 55 V (C3 – 100 A) core-core ≤ 750 V (C1 – 1 kV/500 A) core-ground ≤ 750 V (C2 – 10 kV/5 kA) core-ground ≤ 1.2 kV (C3 – 100 A) core-ground ≤ 80 V (C1 – 1 kV/500 A) core-earth ≤ 125 V (C2 – 10 kV/5 kA) core-earth ≤ 55 V (C3 – 100 A) core-earth |
Response Time (tA) | ≤ 1 ns (core-core), ≤ 1 ns (core-ground), ≤ 100 ns (core-earth) |
Environmental Conditions | |
Operating Temperature | Temperature limits –40 to +85 °C, relative humidity 5% to 95%. |
Mounting | |
Type | EN/IEC60715 TH 35 DIN-Rail. |
Weight | About 60 g. |
Connection | Screw terminal blocks to accommodate terminations up to 2.5 mm² flexible. |
Location | Installation in Safe Area or Zone 2 or Zone 1, Group IIC T4…T6. |
Protection Class | IP20. |
Dimensions | Width 6.2 mm, Depth 83.5 mm, Height 105.8 mm. |