Arya Automation & Otomasyon Çözümleri
📅 --/--/----
USD USD: TRY
EUR EUR: TRY
GBP GBP: TRY

X1-NIS-RLO/SS-02-S SIL2 Solid-State Relay

X1-NIS-RLO/SS-02-S SIL2 Solid-State Relay

Key Features

  • 🔹 SIL 2 / SC 3 Certified
  • 🔹 Installation In Zone 2 / Division 2
  • 🔹 Loop Disconnection To Ease Maintenance Operations
  • 🔹 Up To 2 A Functional / 6 A Inrush Current
  • 🔹 Compatible With DCS / PLC Pulse Testing
  • 🔹 Two Port Isolation: Input / Output
🟢 Active
1 Channel – Product Lifecycle Policy

Connections

Dimensions

Certifications

Type Description Area Number Issued by Issue Date
ATEX FM ATEX zone 2 X1 Series English Certificate ( EN ) Europe FM23ATEX0039X FM 2025-01-13
Ex FM US X1 Series Divisions and Zones English Certificate ( EN ) North America FM23US0073X FM 2025-01-09
Ex FM Canada X1 Series Divisions and Zones English Certificate ( EN ) North America FM23CA0055X FM 2025-01-09
FSM TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx FM IECEx X1 Series English Certificate ( EN ) International IECEx FMG 23.0018X FM 2025-01-09
SIL TUV IT 25 SIL 0531 A SIL Certificate Summary ( EN ) International TUV IT 25 SIL 0531 A TUV_SUD 2025-01-29
UKEx FM UKEx zone 2 X1 Series English Certificate ( EN ) United Kingdom FM23UKEX0040X FM 2025-01-15

Description

General
Power Dissipation 0.3 W @ 24 Vdc System Supply, with 2 A load current, typical.
System In
Voltage 24 Vdc nom (21.5 to 30 Vdc).
Current Consumption 12 mA @ 24 Vdc, typical.
Input Impedance 2 kΩ @ 24 Vdc, typical.
Field Supply
Type AC or DC voltage supply.
Voltage Range 0 to 250 Vac, 0 to 110 Vdc.
Field Out
Type NE load.
Max Ratings 2 A 250 Vac 500 VA, 2 A 110 Vdc 100 W (resistive load).
Max Inrush Current 6 A.
Operate / Release Time ≤ 30 / 30 ms.
Isolation
Test Voltage System In/Field Out 2.5 kV.
Environmental Conditions
Operating Temperature –40 to +60 °C.
Storage Temperature –45 to +80 °C.
Mounting
Type On custom Termination Board. Mix only with electro-mechanical relays (X1-NIS-RLO/EM), input relays (X1-NIS-RLI) or pass-through modules (X1-NIS-PAS).
Weight About 50 g.
Dimensions Width 10 mm, Depth 80 mm, Height 120 mm.

Additional information

GMI-Status

Active

GMI-Series

X1

GMI-Channels

1 N

GMI-Temperature

-40…+70 °C

SIL Seviyesi

SIL 2

GMI-Features

Loop Disconnection Possible

Safety Relay In

Relay Output

WhatsApp Mail