X1-NIS-RLO/SS-02-S SIL2 Solid-State Relay
Key Features
- 🔹 SIL 2 / SC 3 Certified
- 🔹 Installation In Zone 2 / Division 2
- 🔹 Loop Disconnection To Ease Maintenance Operations
- 🔹 Up To 2 A Functional / 6 A Inrush Current
- 🔹 Compatible With DCS / PLC Pulse Testing
- 🔹 Two Port Isolation: Input / Output
Dimensions
Certifications
Type | Description | Area | Number | Issued by | Issue Date |
---|---|---|---|---|---|
ATEX | FM ATEX zone 2 X1 Series English Certificate ( EN ) | Europe | FM23ATEX0039X | FM | 2025-01-13 |
Ex | FM US X1 Series Divisions and Zones English Certificate ( EN ) | North America | FM23US0073X | FM | 2025-01-09 |
Ex | FM Canada X1 Series Divisions and Zones English Certificate ( EN ) | North America | FM23CA0055X | FM | 2025-01-09 |
FSM | TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) | International | TUV IT 22 SIL 0093 | TUV_SUD | 2022-07-25 |
IECEx | FM IECEx X1 Series English Certificate ( EN ) | International | IECEx FMG 23.0018X | FM | 2025-01-09 |
SIL | TUV IT 25 SIL 0531 A SIL Certificate Summary ( EN ) | International | TUV IT 25 SIL 0531 A | TUV_SUD | 2025-01-29 |
UKEx | FM UKEx zone 2 X1 Series English Certificate ( EN ) | United Kingdom | FM23UKEX0040X | FM | 2025-01-15 |
Description
General | |
---|---|
Power Dissipation | 0.3 W @ 24 Vdc System Supply, with 2 A load current, typical. |
System In | |
Voltage | 24 Vdc nom (21.5 to 30 Vdc). |
Current Consumption | 12 mA @ 24 Vdc, typical. |
Input Impedance | 2 kΩ @ 24 Vdc, typical. |
Field Supply | |
Type | AC or DC voltage supply. |
Voltage Range | 0 to 250 Vac, 0 to 110 Vdc. |
Field Out | |
Type | NE load. |
Max Ratings | 2 A 250 Vac 500 VA, 2 A 110 Vdc 100 W (resistive load). |
Max Inrush Current | 6 A. |
Operate / Release Time | ≤ 30 / 30 ms. |
Isolation | |
Test Voltage | System In/Field Out 2.5 kV. |
Environmental Conditions | |
Operating Temperature | –40 to +60 °C. |
Storage Temperature | –45 to +80 °C. |
Mounting | |
Type | On custom Termination Board. Mix only with electro-mechanical relays (X1-NIS-RLO/EM), input relays (X1-NIS-RLI) or pass-through modules (X1-NIS-PAS). |
Weight | About 50 g. |
Dimensions | Width 10 mm, Depth 80 mm, Height 120 mm. |
Additional information
GMI-Status | Active |
---|---|
GMI-Series | X1 |
GMI-Channels | 1 N |
GMI-Temperature | -40…+70 °C |
SIL Seviyesi | SIL 2 |
GMI-Features | Loop Disconnection Possible |
Safety Relay In | Relay Output |