D5295S SIL3 Safety Relay Out Module 5 A NE/ND
Key Features
- 🔹 SIL 3 / SC 3 For NE/ND Loads With ND/NE Driver
- 🔹 SIL 2 / SC 3 For Fault Outputs
- 🔹 Installation In Zone 2
- 🔹 Up To 5 A Functional / 6 A Inrush Current
- 🔹 Load Disconnection On Both Supply Lines Available
- 🔹 High Process Availability To Avoid Spurious Trips
- 🔹 Compatible With DCS / PLC Pulse Testing
- 🔹 Line & Load Short/Open Circuit Detection
- 🔹 Load Voltage Monitoring
- 🔹 Earth Leakage Monitoring
- 🔹 Internal Coil Integrity Monitoring
- 🔹 Field Fault Mirroring To The PLC DO
- 🔹 Modbus RTU RS-485 For Monitor & Configuration
- 🔹 Service Contact Available
- 🔹 Input / Output / Supply Isolation
Dimensions
Certifications
Type | Description | Area | Number | Issued by | Issue Date |
---|---|---|---|---|---|
ATEX | DEKRA ATEX D5000 Relay Series English Certificate ( EN ) | Europe | BVS 10 ATEX E 114 X | DEKRA | 2022-04-12 |
EMC | D5000/D6000 EAC EMC Declaration of Conformity ( RU ) | Eurasian Community | ЕАЭС N RU Д-IT.PA08.B.82326/24 | CONTROL | 2024-09-26 |
Ex | D5000 CCC certificate for China ( EN ) | China | 2020322316000978 | NEPSI | 2024-03-22 |
Ex | CCOE Indian Approval for D5293, D5294, D5295 ( EN ) | India | P424465 | PESO | 2020-07-23 |
Ex | EAC Ex Certificate for D5000 Series (2nd half) ( RU ) | Eurasian Community | ЕАЭС RU С-IT.AA87.В.00765/21 | CCVE | 2021-07-29 |
Ex | Emirates Certificate of Conformity D5000 ( EN ) | United Arab Emirates | 24-05-109026/E24-04-112697/NB0002 | SGS | 2024-05-02 |
Ex | INMETRO Certificate DNV 13.0109 X for D5000 ( EN ) | Brazil | DNV 13.0109 X | DNV | 2022-12-10 |
FSM | TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) | International | TUV IT 22 SIL 0093 | TUV_SUD | 2022-07-25 |
IECEx | DEKRA IECEx for D5000 Series ( EN ) | International | IECEx BVS 10.0072X | DEKRA | 2022-04-14 |
Maritime | KR Maritime Certificate D5000 Series ( EN ) | International | MIL20769-EL002 | KR | 2024-06-26 |
Maritime | DNV Maritime Certificate TAA00001U0 for D5000 series for website ( EN ) | International | TAA00001U0 | DNV-GL | 2024-04-02 |
SIL | TUV C-IS-722160171 SIL Certificate Summary ( EN ) | International | C-IS-722160171 | TUV_SUD | 2022-10-14 |
SIL | TUV C-IS-236198-04 SIL Certificate Summary ( EN ) | International | C-IS-236198-04 | TUV_SUD | 2022-10-14 |
Description
Supply | |
---|---|
Type | 24 Vdc nom (18 to 30 Vdc), reverse polarity protected. |
Current Consumption | 45 mA @ 24 V (no fault), typical. |
Power Dissipation | 1.1 W @ 24 V (no fault), typical. |
Input | |
Type | 24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes. |
Current Consumption | 40 mA @ 24 Vdc (no fault), typical. |
Power Dissipation | 1.0 W @ 24 Vdc (no fault), typical. |
Output | |
Type | Voltage free 2+2 SPST relay contact (2 paralleled contacts in series) at terminals 13-15 and 14-16, open when relay energized, close in de-energized condition. |
Contact Material | Ag Alloy (Cd free), gold plated. |
Contact Rating | 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load). |
Contact Min. Switching Current | 1 mA. |
Contact Inrush Current | 6 A @ 24 Vdc, 250 Vac. |
DC and AC Load Breaking Capacity | Refer to Instruction Manual. |
Contact Current Derating | Refer to Instruction Manual. |
Mechanical / Electrical Life | 5 × 10⁶ / 3 × 10⁴ operations, typical. |
Operate / Release Time | 30 ms / 30 ms, typical. |
Fault | |
Type | Load & line short/open circuit, supply voltage and earth leakage monitor. |
Diagnostics Equivalent Source | When the load is off, the diagnostic circuit forces a sensing signal: 5.5 V open circuit, 10 mA short circuit, typical. |
Line + Load Resistance | Programmable up to 50 kΩ. |
Load Current | Programmable up to 5 A. |
Load Supply Voltage | Programmable up to 250 Vdc/Vac. |
Load Earth Leakage | Programmable up to 3 MΩ. |
Fault Signaling | Voltage free DPST contact. |
Fault 1 Rating | 0.5 A 30 Vac 15 VA, 0.5 A 50 Vdc 25 W (resistive load). |
Fault 2 Rating | 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load). |
Response Time | 4 s, typical. |
Modbus Interface | |
Type | Modbus RTU RS-485 up to 115.2 kbps for monitor/configuration/control. |
Isolation | |
Test Voltage | Output/Input 2.5 kV; Output/Supply 2.5 kV; Output/Fault Outputs 2.5 kV; Output/RS485 Modbus 2.5 kV; Input/Supply 500 V; Input/Fault Output 1 500 V; Input/Fault Output 2 2.5 kV; Input/RS485 Modbus 500 V; Supply/Fault Output 1 500 V; Supply/Fault Output 2 2.5 kV; Supply/RS485 Modbus 500 V. |
Environmental Conditions | |
Operating Temperature | –40 to +70 °C. |
Storage Temperature | –45 to +80 °C. |
Mounting | |
Type | DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. |
Weight | About 235 g. |
Connection | By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
Dimensions | Width 22.5 mm, Depth 123 mm, Height 120 mm. |
Additional information
GMI-Status | Active |
---|---|
GMI-Series | D5000 |
GMI-Channels | 1 N |
SIL Seviyesi | SIL 3 |
GMI-Input-Range | 24 Vdc |
GMI-Output Type | 1 Voltage Free SPDT |
LOAD STATUS | NE / Energize To Trip |
Max Contact Rating | 5 A |
Max Load Voltage | 250 Vdc |
Safety Relay In | Relay Output |
GMI-Temperature | -40…+70 °C |