D5090S-086 Safety Relay Module 5 A NE Loads
KEY FEATURES
- 🔹 SIL 3 / SC 3 FOR NE LOADS WITH NE DRIVER
- 🔹 INSTALLATION IN ZONE 2 / DIV. 2
- 🔹 UP TO 5 A FUNCTIONAL / 6 A INRUSH CURRENT
- 🔹 LOAD DISCONNECTION ON BOTH SUPPLY LINES AVAILABLE
- 🔹 COMPATIBLE WITH DCS / PLC PULSE TESTING
- 🔹 SERVICE CONTACT AVAILABLE
- 🔹 INPUT / OUTPUT ISOLATION
Dimensions
Certifications
Type | Description | Area | Number | Issued by | Issue Date |
---|---|---|---|---|---|
ATEX | DEKRA ATEX D5000 Relay Series English Certificate ( EN ) | Europe | BVS 10 ATEX E 114 X | DEKRA | 2022-04-12 |
EMC | D5000/D6000 EAC EMC Declaration of Conformity ( RU ) | Eurasian Community | ЕАЭС N RU Д-IT.PA08.B.82326/24 | CONTROL | 2024-09-26 |
Ex | D5000 CCC certificate for China ( EN ) | China | 2020322316000978 | NEPSI | 2024-03-22 |
Ex | EAC Ex Certificate for D5000 Series ( RU ) | Eurasian Community | ЕАЭС RU С-IT.AA87.В.01310/24 | CCVE | 2024-06-13 |
Ex | Emirates Certificate of Conformity D5000 ( EN ) | United Arab Emirates | 24-05-109026/E24-04-112697/NB0002 | SGS | 2024-05-02 |
Ex | INMETRO Certificate DNV 13.0109 X for D5000 ( EN ) | Brazil | DNV 13.0109 X | DNV | 2022-12-10 |
FSM | TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) | International | TUV IT 22 SIL 0093 | TUV_SUD | 2022-07-25 |
IECEx | DEKRA IECEx for D5000 Series ( EN ) | International | IECEx BVS 10.0072X | DEKRA | 2022-04-14 |
Maritime | DNV Maritime Certificate TAA00001U0 for D5000 series for website ( EN ) | International | TAA00001U0 | DNV-GL | 2024-04-02 |
SIL | TUV C-IS-236198-04 SIL Certificate Summary ( EN ) | International | C-IS-236198-04 | TUV_SUD | 2022-10-14 |
Description
Input | |
---|---|
Type | 24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes. |
Current Consumption | 45 mA @ 24 Vdc, typical. |
Power Dissipation | 1.1 W @ 24 Vdc, typical. |
Output | |
Type | 1 voltage free SPDT relay contact: – Out 1 (NC contact): terminals 7-11 – Service Load Out (NO contact): terminals 9-10 1 voltage free SPST relay contact: – Out 2 (NC contact): terminals 8-12 Terminals 7-11 and 8-12 are closed when relay is de-energized, open when energized. |
Contact Material | Ag Alloy (Cd free), gold plated. |
Contact Rating | 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load). |
Contact Min. Switching Current | 1 mA. |
Contact Inrush Current | 6 A @ 24 Vdc, 250 Vac. |
DC and AC Load Breaking Capacity | Refer to Instruction Manual. |
Mechanical / Electrical Life | 5 × 10⁶ / 3 × 10⁴ operations, typical. |
Operate / Release Time | 50 / 40 ms typical. |
Isolation | |
Test Voltage | Input / All Outputs 2.5 kV; Out 1 / Out 2 500 V. |
Environmental Conditions | |
Operating Temperature | –40 to +70 °C. |
Storage Temperature | –45 to +80 °C. |
Mounting | |
Type | DIN-Rail 35 mm, or on custom Term. Board. |
Weight | About 125 g. |
Connection | By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
Dimensions | Width 12.5 mm, Depth 123 mm, Height 120 mm. |
Additional information
GMI-Status | Active |
---|---|
GMI-Series | D5000 |
GMI-Channels | 1 N |
SIL Seviyesi | SIL 3 |
GMI-Input-Range | 24 Vdc |
GMI-Output Type | 1 Voltage Free SPDT, Voltage Free SPST OC |
LOAD STATUS | NE / Energize To Trip |
Max Contact Rating | 5 A |
Max Load Voltage | 250 Vdc |
Safety Relay In | Relay Output |
GMI-Temperature | -40…+70 °C |