D1092D-069 SIL 3 Safety Relay Module DIN RAIL
Key Features
- 🔹 SIL3 / SC3 Certified
- 🔹 Installation In Zone 2, Division 2
- 🔹 Two Fully Independent Channels
- 🔹 1 SPST NO Contact And 1 SPST NC Contact For Each Channel
- 🔹 5 A Inrush Current At 30 VDC / 250 VAC
- 🔹 Input / Output Isolation
- 🔹 EMC Compliant: EN61000-6-2, EN61000-6-4, EN61326-1
- 🔹 High Density – Two Channels Per Unit
Dimensions
Certifications
Type | Description | Area | Number | Issued by | Issue Date |
---|---|---|---|---|---|
ATEX | IMQ Zone 2 Applications D1000 Series Certificate ( EN ) | Europe | IMQ 09 ATEX 013 X | IMQ | 2022-05-03 |
EMC | D1000 EAC EMC Declaration of Conformity ( RU ) | Eurasian Community | ЕАЭС N RU Д-IT.НХ37.В.06311/20 | EUROCERT | 2020-08-13 |
Ex | EAC Ex Certificate for D1000 Series ( RU ) | Eurasian Community | ЕАЭС RU С-IT.НА67.В.00113/20 | TECHNOPROGRESS | 2020-09-04 |
Ex | FM No.3024643-3029921C Certificate ( EN ) | North America | 3024643-3029921C | FM | 2005-12-16 |
FSM | TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) | International | TUV IT 22 SIL 0093 | TUV_SUD | 2022-07-25 |
IECEx | IMQ IECEx Zone 2 Applications D1000 Series Certificate ( EN ) | International | IECEx IMQ 13.0011X | IMQ | 2022-05-03 |
Maritime | KR Maritime Certificate D1000 Series ( EN ) | International | MIL20769-EL001 | KR | 2022-07-04 |
Maritime | DNV Maritime Certificate TAA00002BM for D1000 Series ( EN ) | International | TAA00002BM | DNV-GL | 2024-04-05 |
SIL | TUV C-IS-236198-03 SIL Certificate Summary ( EN ) | International | C-IS-236198-03 | TUV_SUD | 2022-10-14 |
Description
Input | |
---|---|
Voltage | 24 Vdc nom (20.4 to 27.6 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
Current Consumption | 50 mA for each channel with relay energized, typical (100 mA for 2 channels D1092D-069 when used as duplicator 1 input / 2 outputs). |
Power Dissipation | 1.2 W for each channel with 24 V input voltage and relay energized, typical (2.4 W for 2 channels D1092D-069 when used as duplicator). |
Max. Power Consumption | At 27.6 V input voltage and relay energized, 1.5 W for each channel (3.0 W for 2 channels D1092D-069 when used as duplicator). |
Output | |
Type | Voltage free SPST NO+SPST NC relay contact. |
Contact Material | Ag Alloy (Cd free). |
Contact Rating | 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load). |
Contact Inrush Current | 5 A at 30 Vdc, 250 Vac. |
Contact Min. Switching Current | 10 mA. |
DC Load Breaking Capacity | See instruction Manual. |
Mechanical / Electrical Life | 50 × 10⁶ / 1 × 10⁵ operations, typical. |
Operate / Release Time | 5 / 3 ms typical. |
Bounce Time NO / NC Contact | 3 ms. |
Frequency Response | 10 Hz maximum. |
Isolation | |
Test Voltage | Input/Output 2.5 KV; Input/Input 500 V; Output/Output 2.5 KV; Output A/Output B 1.5 KV. |
Environmental Conditions | |
Operating | Temperature limits -20 to +60 °C, relative humidity max 95%. |
Storage | Temperature limits -45 to +80 °C. |
Mounting | |
Type | EN/IEC60715 TH 35 DIN-Rail. |
Weight | About 145 g. |
Connection | By polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm². |
Location | Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
Protection Class | IP 20. |
Dimensions | Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |
Additional information
GMI-Status | Phase Out |
---|---|
GMI-Series | D1000 |
GMI-Channels | 2 N |
SIL Seviyesi | SIL 3 |
GMI-Input-Range | 24 Vdc |
Max Load Voltage | 125 Vdc, 250 Vdc |
Safety Relay In | Relay Output |