| Supply Voltage | 24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp |
| Current Consumption | 110 mA with four channels at 20 mA nominal load, 140 mA with short circuit output |
| Power Dissipation | 1.4 W with 24 V supply voltage and four channels at 20 mA nominal load |
| Max. Power Consumption | 3.8 W at 30 V supply voltage and short circuit output |
| Isolation Test Voltage | I.S. Out/Supply 1.5 KV |
| Output | 20 mA at 15 V per channel (20.5 V no load, 273 Ω series resistance) |
| Short Circuit Current | ≥ 24 mA per channel (26 mA typical) |
| Operating Temperature | -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C |
| Storage Temperature | -45 to + 80 °C |
| Safety Parameters | Uo/Voc = 23.6 V, Io/Isc = 88.2 mA, Po/Po = 519 mW at terminals 13-14, 15-16, 9-10, 11-12. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C |
| Mounting | EN/IEC60715 TH 35 DIN-Rail |
| Weight | about 120 g |
| Connection | by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2 |
| Location | Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation |
| Protection Class | IP 20 |
| Dimensions | Width 22.5 mm, Depth 99 mm, Height 114.5 mm |