Arya Automation & Otomasyon Çözümleri
📅 --/--/----
USD USD: TRY
EUR EUR: TRY
GBP GBP: TRY

D2050M Intrinsically Safe Digital Multiplexer

D2050M Intrinsically Safe Digital Multiplexer

Key Features

  • 🔹 Intrinsically Safe Associated Apparatus For Safe Area Use
  • 🔹 Supports D2010M / D2011M / D2030M In Hazardous Locations
  • 🔹 Expandable Up To 7936 Analog / 3968 Digital Channels
  • 🔹 Modbus RTU Over Redundant RS-485, Plus RS-232 Config Port
  • 🔹 Three Port Isolation: Input / Output / Supply
  • 🔹 EMC Compliant: EN61000-6-2, EN61000-6-4
  • 🔹 Configurable Via SWC2090 Or Custom Software
  • 🔹 Repeat Inputs To Safe Area Using D2052M (Relay) Or D2053M (Transistor)
🟢 Active
Discover D2000 – Product Lifecycle Policy

Certifications

Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D2000 System English Certificate ( EN ) Europe BVS 06 ATEX E 101 X EXAM 2018-05-29
EMC D2000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.НХ37.В.06310/20 EUROCERT 2020-08-13
Ex D2000 CCC certificate for China ( EN ) China 2020322316000820 NEPSI 2023-04-30
Ex EAC Ex Certificate for D2000 Series ( RU ) Eurasian Community ЕАЭС RU С-IT.НА67.В.00106/20 TECHNOPROGRESS 2020-08-21
Ex FM No.3024643-3029921C Certificate ( EN ) North America 3024643-3029921C FM 2005-12-16
IECEx DEKRA IECEx for D2000 Series ( EN ) International IECEx BVS 09.0049X DEKRA 2013-11-29
Metrological Metrological Certificate Russia for D2000 Series ( RU ) Russia 46390-11 ROSSTANDART 2021-03-10

Connections

Description

Supply
Voltage 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
Current Consumption @ 24 V 260 mA with four multiplexer unit connected typical.
Power Dissipation 5.0 W with 24 V supply voltage and four multiplexer unit connected.
Max. Power Consumption At 30 V supply and output short circuit condition 8.5 W.
Input/Output I.S. Hazardous Area
Type Dual serial communication line, proprietary protocol and power to supply field multiplexer unit D2010M or D2030M (up to four).
Scan Cycle Time 50 ms for a system with 4 D2030M unit (128 digital channel), 1700 ms for a system with 4 D2010M and 12 D2011M (256 analog channel).
Output/Input Safe Area
Type Modbus RTU protocol up to 115.2 Kbit/s with RS-485 redundant connection.
Terminating Impedance 250 Ω DIP-switch selectable.
Transmission Speed 4.8, 9.6, 19.2, 38.4, 57.6, 115.2 Kbit/s.
Transmission Cable Length ≤ 1200 m up to 93.75 Kbit/s, ≤ 1000 m up to 115.2 Kbit/s.
Configuration Line
Type RS232 connection (EIA RS232-C applicable standard).
Transmission Speed 19.2 Kbit/s.
Transmission Cable Length ≤ 15 m.
Connection SUB D 9 poles male connector (requires female mating connector).
Isolation
Test Voltage I.S. Out/RS-232 Configuration Line 1.5 KV; I.S. Out/RS-485 Modbus Line 1.5 KV; I.S. Out/Supply 1.5 KV; RS-232 Configuration Line/Supply 500 V; RS-485 Modbus Line/Supply 500 V; RS-232 Configuration Line/RS-485 Modbus Line 500 V.
Environmental Conditions
Operating Temperature limits –40 to +60 °C, relative humidity max 90 % non-condensing, up to 35 °C.
Storage Temperature limits –45 to +80 °C.
Safety Description
Safety Parameters Um = 250 Vrms, -40 °C ≤ Ta ≤ 60 °C.
Mounting
Type T35 DIN Rail according to EN50022.
Weight About 570 g.
Connection By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
Location Safe Area/Non Hazardous Locations installation.
Protection Class IP 20.
Dimensions Width 127 mm, Length 220 mm, Depth 78 mm.

Additional information

GMI-Status

Active

Multiplexer Systems

Intrinsically Safe Multiplexer System

Max Load Voltage

24 Vdc

WhatsApp Mail