Arya Automation & Otomasyon Çözümleri
📅 --/--/----
USD USD: TRY
EUR EUR: TRY
GBP GBP: TRY

D2010M Intrinsically Safe Temperature Multiplexer

D2010M Intrinsically Safe Temperature Multiplexer

Key Features

  • 🔹 Intrinsically Safe For Zone 1, 2, Class I/Div 1,2, Group IIC, IIA, IIB
  • 🔹 Universal Inputs: mV, Thermocouples, RTD From Zone 0, 1, 2
  • 🔹 200 V / 60 V / 500 V Isolation For Safe Sensor Grounding
  • 🔹 Expandable Up To 7936 Channels Over Modbus
  • 🔹 Redundant Field Communication/Supply Lines
  • 🔹 18-Bit High Accuracy A/D Converter
  • 🔹 16 Channels Per Unit – 256 Channels Per System
  • 🔹 Easy Configuration via D2050M Gateway & Free SWC2090 Software
  • 🔹 Cost-Effective – Reduces PLC/DCS I/O Card Requirements
🟢 Active
16 Channels – Product Lifecycle Policy

Certifications

Type Description Area Number Issued by Issue Date
ATEX DEKRA ATEX D2000 System English Certificate ( EN ) Europe BVS 06 ATEX E 101 X EXAM 2018-05-29
EMC D2000 EAC EMC Declaration of Conformity ( RU ) Eurasian Community ЕАЭС N RU Д-IT.НХ37.В.06310/20 EUROCERT 2020-08-13
Ex D2000 CCC certificate for China ( EN ) China 2020322316000820 NEPSI 2023-04-30
Ex EAC Ex Certificate for D2000 Series ( RU ) Eurasian Community ЕАЭС RU С-IT.НА67.В.00106/20 TECHNOPROGRESS 2020-08-21
Ex FM No.3024643-3029921C Certificate ( EN ) North America 3024643-3029921C FM 2005-12-16
IECEx DEKRA IECEx for D2000 Series ( EN ) International IECEx BVS 09.0049X DEKRA 2013-11-29
Metrological Metrological Certificate Russia for D2000 Series ( RU ) Russia 46390-11 ROSSTANDART 2021-03-10

Connections

Description

Supply
Voltage Via D2050M gateway unit.
Max. Power Consumption 200 mW.
Input
Type Millivolt or thermocouple type A1, A2, A3, B, E, J, K, L DIN, L GOST, N, R, S, S GOST, T, U or 3-4 wires RTD Pt100, Pt200, Pt300 to DIN43760, Pt100 (0.3916), Ni 100 or Pt100, Pt50, Cu100, Cu53, Cu50, Cu 46 (GOST) or mA signals with external shunt (D1090Q) or V signals with external divider (D1094Q).
Input Channels 16 for mV, RTD or TC without automatic reference junction compensator or 15 using automatic reference junction compensator for thermocouples inputs (channel 16 is used for compensator connection).
Resolution 2 μV on mV or thermocouple, 10 mΩ on RTD.
Input Range Within sensor’s rated limits; mV range from -21 to +80 mV or -21 to +21 mV, resistance range from 0.0 to 400.0 Ω.
Measuring RTD Current ≤ 200 μA.
RTD Line Resistance Compensation ≤ 10 Ω.
Thermocouple Reference Junction Compensation Automatic with external sensor on channel nr. 16 (OPT2091 separately ordered or user selectable RTD) or fixed programmable from -60 to +100 °C.
Burnout Up, down or disabled.
Scan Cycle Time 1700 ms for a system with 4 D2010M and 12 D2011M (256 ch.).
Performance
Type Field units powered by D2050M gateway at 23 ± 1 °C ambient temperature.
Calibration and Linearity Accuracy ≤ ±20 μV on mV or thermocouple, 200 mΩ on RTD or ±0.05 % of input value, whichever is greater.
Temperature Influence ≤ ±2 μV, 10 mΩ or ±0.01 % of input value for a 1 °C change.
Reference Junction Compensation Influence ≤ ±1 °C (thermocouple sensors only).
Isolation
Test Voltage I.S. In/Supply-Communication line 500 V; I.S. In/I.S. In 200 V for mV/TC, 60 V for RTD; I.S. In/Ground 500 V; I.S. In/I.S. In between units 500 V. Communication line/Ground 500 V.
Environmental Conditions
Operating Temperature limits –40 to +60 °C, relative humidity max 90 % non-condensing, up to 35 °C.
Storage Temperature limits –45 to +80 °C.
Safety Description
Safety Parameters Uo/Voc = 10.7 V, Io/Isc = 7 mA, Po/Po = 19 mW at terminals 1-2-3-4 of channel 1 to 16. -40 °C ≤ Ta ≤ 60 °C.
Mounting
Type T35 DIN Rail according to EN50022.
Weight About 750 g.
Connection By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
Location Safe Area/Non Hazardous Locations or Zone 1, 2, Group IIC, IIB, IIA T4, Class I, Division 1, Groups A, B, C, D Temperature Code T4 and Class I, Zone 1, 2, Group IIC, IIB, IIA T4 installation.
Protection Class IP 20.
Dimensions Width 127 mm, Length 220 mm, Depth 78 mm.

Additional information

GMI-Status

Active

GMI-Channels

16 N.

Multiplexer Systems

Intrinsically Safe Multiplexer System

GMI-Temperature

-40…+60 °C

WhatsApp Mail