Supply Voltage |
24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp |
Current Consumption |
110 mA with four channels at 20 mA nominal load, 140 mA with short circuit output |
Power Dissipation |
1.4 W with 24 V supply voltage and four channels at 20 mA nominal load |
Max. Power Consumption |
3.8 W at 30 V supply voltage and short circuit output |
Isolation Test Voltage |
I.S. Out/Supply 1.5 KV |
Output |
20 mA at 15 V per channel (20.5 V no load, 273 Ω series resistance) |
Short Circuit Current |
≥ 24 mA per channel (26 mA typical) |
Operating Temperature |
-20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C |
Storage Temperature |
-45 to + 80 °C |
Safety Parameters |
Uo/Voc = 23.6 V, Io/Isc = 88.2 mA, Po/Po = 519 mW at terminals 13-14, 15-16, 9-10, 11-12. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C |
Mounting |
EN/IEC60715 TH 35 DIN-Rail |
Weight |
about 120 g |
Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2 |
Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation |
Protection Class |
IP 20 |
Dimensions |