D1063S Gauge Bridge Isolating Repeater Isolator
Ürün Özellikleri
- 🔹 Zone 0 (Zone 20), Division 1’den Giriş, Zone 2, Division 2’ye Kurulum
- 🔹 Strain Gauge Köprü Tipi Şeffaf Tekrarlayıcı
- 🔹 4×350 Ω, 6×450 Ω veya 12×1000 Ω Yük Hücresi ile Uyumlu
- 🔹 Saha Kablo Kopma Hatası Algılama
- 🔹 Yüksek Doğruluk
- 🔹 Giriş/Çıkış/Güç Arasında Üçlü İzolasyon
- 🔹 EN61000-6-2, EN61000-6-4 ile EMC Uyumluluğu
- 🔹 DIP Switch ile Sahada Programlanabilirlik
- 🔹 250 Vrms (Um) Maksimum İzin Verilen Gerilim
🟢 Phase Out
Discover D1000
Discover D1000
Connections
Description
Type | Description |
---|---|
Supply Voltage | 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
Current Consumption | 80 mA with four 350 Ω load cells connected, typical. |
Power Dissipation | 1.7 W with 24 V supply and four 350 Ω load cells connected typical. |
Max. Power Consumption | At 30 V supply voltage and short circuit input, 2.8 W. |
Input Type | Up to four 350 Ω, six 450 Ω, or twelve 1000 Ω load cells in parallel. |
Bridge Supply Voltage | 4.5 V nominal. |
Bridge Output Signal | ≤ 4 mV/V. |
Input Range | ± 18 mV nominal span, ± 22 mV overrange. |
Line Resistance Compensation | ≤ 10 Ω. |
Burnout Type | LED indication for field wire breakage. |
Output Type | ± 20 mV nominal span, ± 24 mV overrange (5 V ref); ± 40 mV nominal span, ± 48 mV overrange (10 V ref). |
Output Impedance | 350 Ω typical. |
Host Reference Voltage | ≤ 10 V typical, ≤ 11 V maximum. |
Internal Reference Voltage | 10 V typical, DIP switch settable. |
Internal Impedance | 350 Ω typical, DIP switch settable. |
Transfer Characteristic | Linear based on mV input. |
Response Time | ≤ 100 ms (10 to 90 % step change). |
Performance Type | Ref. conditions 24 V supply, 23 ± 1 °C ambient temperature. |
Calibration Accuracy | ≤ ± 0.003 % of full scale of input range. |
Linearity Accuracy | ≤ ± 0.002 % of full scale of input range. |
Supply Voltage Influence | ≤ ± 0.002 % of full scale for a min to max supply change. |
Temperature Influence | ≤ ± 0.002 % of full scale of input range for a 1 °C change. |
Isolation Test Voltage | I.S. In/Out 1.5 kV; I.S. In/Supply 1.5 kV; Out/Supply 500 V. |
Operating Conditions | Temperature limits –20 to +60 °C, RH max 90 % non-condensing up to 35 °C. |
Storage Conditions | Temperature limits –45 to +80 °C. |
Safety Parameters | Uo = 17.3 V, Io = 199.6 mA, Po = 864 mW at terminals 9–14; Ui = 30 V, Ci = 0 nF, Li = 0 nH; Um = 250 Vrms, –20 °C ≤ Ta ≤ 60 °C. |
Mounting Type | EN/IEC60715 TH 35 DIN-Rail. |
Weight | About 165 g. |
Connection | By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm². |
Location | Safe Area/Non Hazardous or Zone 2, Class I, Div 2, Group IIC T4 installations. |
Protection Class | IP 20. |
Dimensions | Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |
Additional information
GMI-Applications | Load Cell Input |
---|