Arya Automation & Otomasyon Çözümleri
📅 --/--/----
USD USD: TRY
EUR EUR: TRY
GBP GBP: TRY

D1054S SIL 2 Repeater Power Supply & Trip Amplifiers

D1054S SIL 2 Repeater Power Supply & Trip Amplifiers

Ürün Özellikleri

  • 🔹 SIL2 / SC2 Uyumlu
  • 🔹 Zone 0 (Zone 20), Division 1 Giriş – Zone 2, Division 2 Kurulum
  • 🔹 4-20 mA Loop veya 0/4-20 mA Harici Güçlü Giriş Sinyali
  • 🔹 0/4-20 mA, 0/1-5 V, 0/2-10 V Çıkış – Lineer veya Ters
  • 🔹 Geniş Bant HART® Uyumlu Akıllı İletişim
  • 🔹 Giriş ve Çıkış Kısa Devre Koruması
  • 🔹 İki Bağımsız Trip Rölesi
  • 🔹 Arıza Tespiti için Çıkış (Burnout Detection)
  • 🔹 Yüksek Hassasiyet – Mikroişlemci Kontrollü A/D Dönüştürücü
  • 🔹 3 Port İzolasyon: Giriş / Çıkış / Besleme
  • 🔹 EMC Uyumu: EN61000-6-2, EN61000-6-4, EN61326-1
  • 🔹 Tam Programlanabilir Çalışma Parametreleri
  • 🔹 Maks. 250 Vrms (Um) İzin Verilen Gerilim
🔍 Discover D1000
🟡 SPARE-ONLY
Sonraki Aşama: OBSOLETE (31.12.2025)

Data Sheet

Data Sheet
  • Datasheet of D1010 (EN)
  • D1000 Series Common Specifications and Dimensional Drawing (EN)
Instruction Manual
  • Instruction Manual D1010 (EN)
  • Instruction Manual D1000 Series (EN | RU)
  • Ex Safety Instruction Manual for D1000 Series (EN | IT)
  • Ex Safety Instruction Manual for D1000 Series (IT)
  • INMETRO Safety Instruction Manual for D1000 Series (PT)
  • UL Control Drawing D1010 (EN)

Dimensions

Approvals

Type Description Area Number Issued By Issue Date
ATEX DEKRA ATEX D1000 Series English Certificate (EN) Europe DMT 01 ATEX E 042 X DEKRA 2022-04-25
ATEX IMQ Zone 2 Applications D1000 Series Certificate (EN) Europe IMQ 09 ATEX 013 X IMQ 2022-05-03
EMC D1000 EAC EMC Declaration of Conformity (RU) Eurasian Community ЕАЭС N RU Д-IT.НХ37.В.06311/20 EUROCERT 2020-08-13
Ex EAC Ex Certificate for D1000 Series (RU) Eurasian Community ЕАЭС RU С-IT.НА67.В.00113/20 TECHNOPROGRESS 2020-09-04
Ex UL-cUL D1010, D1020 Divisions and Zones (EN) North America 20130115-E222308C UL 2013-01-15
Ex FM No.3024643-3029921C Certificate (EN) North America 3024643-3029921C FM 2005-12-16
Ex INMETRO Certificate DNV 13.0108 X for D1000 Series (EN) Brazil DNV 13.0108 X DNV 2022-12-10
FSM TUV IT 22 SIL 0093 Functional Safety Certificate (EN) International TUV IT 22 SIL 0093 TUV_SUD 2022-07-25
IECEx IMQ IECEx Zone 2 Applications D1000 Series Certificate (EN) International IECEx IMQ 13.0011X IMQ 2022-05-03
IECEx DEKRA IECEx for D1000 Series (EN) International IECEx BVS 07.0027X DEKRA 2022-05-30
Maritime KR Maritime Certificate D1000 Series (EN) International MIL20769-EL001 KR 2022-07-04
Maritime DNV Maritime Certificate TAA00002BM for D1000 Series (EN) International TAA00002BM DNV-GL 2024-04-05
Metrological Metrological Certificate Russia for D1000 Series (RU) Russia 64283-11 ROSSTANDART 2021-03-10
SIL TUV C-IS-236198-03 SIL Certificate Summary (EN) International C-IS-236198-03 TUV_SUD 2022-10-14

Connections

Description

Type Description
Supply Type 12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp
Supply Current Consumption 90 mA with 20 mA input/output and relays energized
Supply Power Dissipation 1.7 W with 24 V supply, 20 mA input/output and relays energized.
Supply Max. power consumption at 30 V supply voltage, input short circuit, overload condition, relays energized and PPC1090 connected, 2.9 W.
Input Type 0/4 to 20 mA (separately powered input, voltage drop ≤ 1 V) or 4 to 20 mA (2 wire Tx current limited at ≈ 25 mA).
Input Integration time 100 ms
Input Resolution 1 µA.
Input Input range 0 to +22 mA
Transmitter line voltage Type ≥ 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 40 KHz frequency band.
Burnout Type enabled or disabled. Analog output can be programmed to detect burnout condition with downscale or highscale forcing. Alarms can be programmed to detect burnout condition.
Burnout Range low and high separated trip point value programmable between -5 to +25 mA.
Output Type 0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V.
Output Resolution 1 µA current output or 1 mV voltage output.
Output Transfer characteristic linear or reverse.
Output Response time ≤ 50 ms (10 to 90 % step change).
Output Output ripple ≤ 20 mVrms on 250 Ω communication load on 0.5 to 40 KHz band.
Output Frequency response 0.5 to 40 KHz bidirectional within 3 dB (HART® and higher frequency protocols) only with mA direct current output.
Alarm Trip point range within rated limits of input sensor (see input for step resolution).
Alarm ON-OFF delay time 0 to 1000 s, 100 ms step, separate setting.
Alarm Hysteresis 0 to 5 mA (see input for step resolution).
Alarm Output voltage free SPST relay contact.
Alarm Contact rating 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load).
Performance Type Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Performance Input Calibration and linearity accuracy: ≤ ± 20 μA Temperature influence: ≤ ± 1 μA of input for a 1 °C change.
Performance Analog Output Calibration accuracy: ≤ ± 0.1 % of full scale. Output Linearity error: ≤ ± 0.05 % of full scale. Supply voltage influence: ≤ ± 0.05% of full scale for min to max supply change Load influence: ≤ ± 0.05% of full scale for 0 to 100 % load resistance change Temperature influence: ≤ ± 0.01 % on zero and span for a 1 °C change.
Isolation Test Voltage I.S. In/Outs 1.5 KV; I.S. In/Supply 1.5 KV; Analog Out/Supply 500 V; Analog Out/Alarm Outs 1.5 KV; Alarm Outs/Supply 1.5 KV; Alarm Out/Alarm Out 1.5 KV.
Environmental conditions Operating temperature limits -20 to + 60 °C, relative humidity max 95 %.
Environmental conditions Storage temperature limits – 45 to + 80 °C.
Safety description Safety parameters Uo/Voc = 26.3 V, Io/Isc = 91 mA, Po/Po = 597 mW at terminals 14-15. Uo/Voc = 1.1 V, Io/Isc = 56 mA, Po/Po = 16 mW at terminals 15-16. Ui/Vmax = 30 V, Ii/Imax = 128 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C.
Mounting Type EN/IEC60715 TH 35 DIN-Rail.
Mounting Weight about 175 g.
Mounting Connection by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Mounting Location Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Mounting Protection class IP 20.
Mounting Dimensions Width 22.5 mm, Depth 99 mm, Height 114.5 mm.