Supply Type |
12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp |
Supply Current Consumption |
90 mA with 20 mA input/output and relays energized |
Supply Power Dissipation |
1.7 W with 24 V supply, 20 mA input/output and relays energized. |
Supply Max. power consumption |
at 30 V supply voltage, input short circuit, overload condition, relays energized and PPC1090 connected, 2.9 W. |
Input Type |
0/4 to 20 mA (separately powered input, voltage drop ≤ 1 V) or 4 to 20 mA (2 wire Tx current limited at ≈ 25 mA). |
Input Integration time |
100 ms |
Input Resolution |
1 µA. |
Input Input range |
0 to +22 mA |
Transmitter line voltage Type |
≥ 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 40 KHz frequency band. |
Burnout Type |
enabled or disabled. Analog output can be programmed to detect burnout condition with downscale or highscale forcing. Alarms can be programmed to detect burnout condition. |
Burnout Range |
low and high separated trip point value programmable between -5 to +25 mA. |
Output Type |
0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V. |
Output Resolution |
1 µA current output or 1 mV voltage output. |
Output Transfer characteristic |
linear or reverse. |
Output Response time |
≤ 50 ms (10 to 90 % step change). |
Output Output ripple |
≤ 20 mVrms on 250 Ω communication load on 0.5 to 40 KHz band. |
Output Frequency response |
0.5 to 40 KHz bidirectional within 3 dB (HART® and higher frequency protocols) only with mA direct current output. |
Alarm Trip point range |
within rated limits of input sensor (see input for step resolution). |
Alarm ON-OFF delay time |
0 to 1000 s, 100 ms step, separate setting. |
Alarm Hysteresis |
0 to 5 mA (see input for step resolution). |
Alarm Output |
voltage free SPST relay contact. |
Alarm Contact rating |
2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). |
Performance Type |
Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature. |
Performance Input |
Calibration and linearity accuracy: ≤ ± 20 μA Temperature influence: ≤ ± 1 μA of input for a 1 °C change. |
Performance Analog Output |
Calibration accuracy: ≤ ± 0.1 % of full scale. Output Linearity error: ≤ ± 0.05 % of full scale. Supply voltage influence: ≤ ± 0.05% of full scale for min to max supply change Load influence: ≤ ± 0.05% of full scale for 0 to 100 % load resistance change Temperature influence: ≤ ± 0.01 % on zero and span for a 1 °C change. |
Isolation Test Voltage |
I.S. In/Outs 1.5 KV; I.S. In/Supply 1.5 KV; Analog Out/Supply 500 V; Analog Out/Alarm Outs 1.5 KV; Alarm Outs/Supply 1.5 KV; Alarm Out/Alarm Out 1.5 KV. |
Environmental conditions Operating |
temperature limits -20 to + 60 °C, relative humidity max 95 %. |
Environmental conditions Storage |
temperature limits – 45 to + 80 °C. |
Safety description Safety parameters |
Uo/Voc = 26.3 V, Io/Isc = 91 mA, Po/Po = 597 mW at terminals 14-15. Uo/Voc = 1.1 V, Io/Isc = 56 mA, Po/Po = 16 mW at terminals 15-16. Ui/Vmax = 30 V, Ii/Imax = 128 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C. |
Mounting Type |
EN/IEC60715 TH 35 DIN-Rail. |
Mounting Weight |
about 175 g. |
Mounting Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
Mounting Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
Mounting Protection class |
IP 20. |
Mounting Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |