Control Input Type |
switch contact, logic level reverse polarity protected. |
Control Input Trip Voltage |
OFF ≤ 5.0 V, ON ≥ 20.0 V (max 30 V). |
Control Input Current |
5 mA @ 24 V. |
Override Input Type |
override control signal de-energizes output when enabled by dip-switch. |
Override Input Range |
24 Vdc nom (20 to 30 Vdc) to disable; 0 to 5 Vdc to de-energize, reverse polarity protected. |
Override Input Current |
5 mA @ 24 V. |
Output Type |
45 mA at 13.0 V (Out A), 10.2 V (Out B), 8.5 V (Out C). |
Short Circuit Current |
≥ 50 mA (55 mA typical). |
Response Time |
≤ 10 ms. |
Frequency Response |
50 Hz. |
Fault Detection Type |
open/short circuit detection with dip-switch; output de-energized until fault is cleared. |
Short Output Detection |
load ≤ 50 Ω (≈ 2 mA forcing). |
Open Output Detection |
load > 10 KΩ. |
Fault Signalling Type |
voltage free NE SPST optocoupled open-collector transistor. |
Open-Collector Rating |
100 mA at 35 Vdc (≤ 1.5 V drop). |
Leakage Current |
≤ 50 µA at 35 Vdc. |
Fault Response Time |
≤ 5 ms. |
Isolation Test Voltage |
I.S. Out/In/Fault/Override 1.5 KV; others 500 V. |
Operating Conditions |
-20 to + 60 °C, RH max 90 %, non condensing. |
Storage Conditions |
-45 to + 80 °C. |
Safety Parameters |
Uo/Voc = 24.8 V, Io/Isc = 147/108/93 mA (Out A/B/C), Po/Po = 907/667/571 mW. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
Mounting |
EN/IEC60715 TH 35 DIN-Rail. |
Weight |
about 135 g. |
Connection |