Output Module Voltage |
24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
Output Module Current Consumption |
90 mA @24 V with output energized at nominal load, 110 mA @24 V with short circuit output. |
Output Module Power Dissipation |
1.4 W with 24 V supply voltage, output energized at nominal load. |
Output Module Max. Power Consumption |
at 30 V supply voltage and short circuit output, 2.9 W |
Output Module Input Type |
switch contact, logic level or loop powered. |
Output Module Trip Voltage Levels |
OFF status ≤ 1.0 V, ON status ≥ 6.0 V (maximum 30 V) |
Output Module Input Current Consumption |
3 mA @24 V(≈ 10 KΩ input impedance). |
Output Module Output Type |
70 mA at 11.3 V (Out A), 70 mA at 12.2 V (Out B) |
Output Module Short Circuit Current |
≥ 85 mA (90 mA typical) |
Output Module Response Time |
20 ms (power up in 600 ms typical in loop powered mode). |
Output Module Test Voltage |
I.S. Out/In 1.5 KV; I.S. Out/Supply 1.5 KV; In/Supply 500 V; In/In 500 V |
Output Module Operating Conditions |
-20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. |
Output Module Storage Conditions |
– 45 to + 80 °C. |
Output Module Safety Parameters |
Uo/Voc = 18.9 V, Io/Isc = 249 mA, Po/Po = 1173 mW (Out A), 1286 mW (Out B). Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
Output Module Mounting |
EN/IEC60715 TH 35 DIN-Rail. |
Output Module Weight |
about 130 g. |
Output Module Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
Output Module Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
Output Module Protection Class |
IP 20. |
Output Module Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |