Supply Voltage |
24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
Supply Current Consumption |
130 mA with four channels energized at nominal load, 150 mA with short circuit output |
Supply Power Dissipation |
2.3 W with 24 V supply voltage and four channels energized at nominal load. |
Supply Max. power consumption |
at 30 V supply voltage and short circuit output, 4.0 W |
Input Type |
switch contact, logic level common positive or common negative or loop powered. |
Input Trip voltage levels |
OFF status ≤ 1.0 V, ON status ≥ 6.0 V (maximum 30 V). |
Input Current Consumption |
3 Ma @24V (≈ 10 KΩ input impedance). |
Output Type |
22 mA at 13.2 V per channel (20.5 V no load, 334 Ω series resistance). |
Output Short circuit current |
≥ 24 mA per channel (26 mA typical) |
Output Response time |
20 ms (power up in 600 ms typical in loop powered mode). |
Isolation Test Voltage |
I.S. Out/In 1.5 KV; I.S. Out/Supply 1.5 KV; In/Supply 500 V. |
Environmental conditions Operating |
temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. |
Environmental conditions Storage |
temperature limits -45 to + 80 °C. |
Safety description Safety parameters |
Uo/Voc = 23.6 V, Io/Isc = 72 mA, Po/Po = 424 mW at terminals 13-14,15-16,9-10,11-12. |
Mounting Type |
EN/IEC60715 TH 35 DIN-Rail. |
Mounting Weight |
about 130 g. |
Mounting Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
Mounting Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
Mounting Protection class |
IP 20. |
Mounting Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |