Supply Voltage |
No supply voltage required because loop-powered. |
Supply Power Dissipation |
≤ 1.1 W per channel at 40 mA, 30 V loop supply. |
Output Type |
1 to 40 mA. |
Output Output characteristic (typical) |
Vout = (Vin – 1.5) – (0.4 x Iout) for 6 V < Vin < 23 V. Vout = 22 – (0.4 x Iout) for 23 V < Vin < 30 V. 4-20 mA output on load of 100 to 600 Ω; Accuracy ≤ 1 %. |
Output Response time |
50 ms (10 to 90 % step change). |
Input Range |
6 to 30 V (loop powered). |
Input Input current |
1 to 40 mA (loop powered) |
Input Voltage drop-out |
9.5 V at 20 mA and with 500 Ω load. |
Input Open circuit consumption |
≤ 0.4 mA at 20 V |
Performance Reference ambient temperature conditions |
23 ± 1 °C. |
Performance Current transfer error |
≤ 400 µA (6 V |
Performance Temperature influence |
≤ ± 0.01 % for a 1 °C change. |
Isolation Test Voltage |
I.S. Out/In 1.5 KV; I.S. Out/I.S. Out 500 V; In/In 500 V. |
Environmental conditions Operating |
temperature limits -20 to + 60 °C,relative humidity max 90 % non condensing, up to 35 °C. |
Environmental conditions Storage |
temperature limits – 45 to + 80 °C. |
Safety description Safety parameters |
Uo/Voc = 25.2 V, Io/Isc = 93 mA, Po/Po = 581 mW at terminals 13-14, 15-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
Mounting Type |
EN/IEC60715 TH 35 DIN-Rail. |
Mounting Weight |
about 125 g |
Mounting Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
Mounting Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
Mounting Protection class |
IP 20. |
Mounting Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |