Supply Voltage |
12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
Supply Current Consumption |
110 mA with 20 mA output typical |
Supply Power Dissipation |
1.8 W with 24 V supply voltage and 20 mA output typical |
Supply Max. power consumption |
at 30 V supply voltage and short circuit condition, 3.4 W |
Input Type |
4 to 20 mA (2 wire Tx current limited at ≈ 25 mA). |
Input Transmitter line voltage |
≥ 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 2.5 KHz frequency band. |
Output Type |
4 to 20 mA, on max. 600 Ω load in source mode; V min. 5 V at 0 Ω load V max. 30 V in sink mode, current limited at ≈ 25 mA or 1 to 5 V on internal 250 Ω shunt (or 2 to 10 V on internal 500 Ω shunt on request). |
Output Response time |
20 ms (10 to 90 % step change). |
Output Output ripple |
≤ 20 mVrms on 250 Ω communication load on 0.5 to 2.5 KHz band. |
Output Frequency response |
0.5 to 2.5 KHz bidirectional within 3 dB (HART® protocol). |
Performance Type |
Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature. |
Performance Calibration accuracy |
≤ ± 0.1 % of full scale. |
Performance Linearity error |
≤ ± 0.1 % of full scale. |
Performance Supply voltage influence |
≤ ± 0.05 % of full scale for a min to max supply change. |
Performance Load influence |
≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change. |
Performance Temperature influence |
≤ ± 0.01 % on zero and span for a 1 °C change. |
Isolation Test Voltage |
I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V. |
Environmental conditions Operating |
temperature limits -20 to + 60 °C, relative humidity max 95 %. |
Environmental conditions Storage |
temperature limits – 45 to + 80 °C. |
Safety description Safety parameters |
Uo/Voc = 25.2 V, Io/Isc = 93 mA, Po/Po = 585 mW at terminals 14-15, 10-11. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
Mounting Type |
EN/IEC60715 TH 35 DIN-Rail. |
Mounting Weight |
about 170 g |
Mounting Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
Mounting Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
Mounting Protection class |
IP 20. |
Mounting Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |