Supply Type |
24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
Supply Current Consumption |
40 mA with 20 mA output typical. |
Supply Power Dissipation |
0.9 W with 24 V supply voltage and 20 mA output typical |
Supply Max. power consumption |
at 30 V supply voltage and overload condition 1.2 W. |
Input Type |
-5 to +35 mV |
Output Type |
4 to 20 mA, on 250 Ω load in source mode. |
Output Response time |
25 ms (10 to 90 % step change) with 8.6 dB of NMRR. |
Output Common mode rejection |
better than 80 dB. |
Output Output ripple |
≤ 20 mVrms on 250 Ω load. |
Output Burnout |
Upscale in 25 ms. |
Performance Type |
Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature |
Performance Calibration accuracy |
≤ ± 0.1 % of full scale |
Performance Linearity error |
≤ ± 0.1 % of full scale |
Performance Supply voltage influence |
≤ ± 0.02 % of full scale for a min to max supply change. |
Performance Load influence |
≤ ± 0.02 % of full scale for a 0 to 100 % load resistance change. |
Performance Stability |
estimated degradation in 3 years ≤ ± 0.47 % least sensitive range. |
Isolation Test Voltage |
I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; Out/Supply 500 V |
Environmental conditions Operating |
temperature limits -20 to + 60 °C, relative humidity max 95 %. |
Environmental conditions Storage |
temperature limits -45 to + 80 °C. |
Safety description Safety parameters |
Uo/Voc = 1.1 V, Io/Isc = 38 mA, Po/Po = 11 mW at terminals 15-16. Ui/Vmax = 30 V, Ii/Imax = 104 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
Mounting Type |
EN/IEC60715 TH 35 DIN-Rail. |
Mounting Weight |
about 110 g. |
Mounting Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
Mounting Location |
Safe Area or Zone 2, Group IIC T4 installation. |
Mounting Protection class |
IP 20. |
Mounting Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |