| Supply |
|---|
| Type | 24 Vdc nom (18 to 30 Vdc), reverse polarity protected. |
| Current Consumption | 15 mA @ 24 V, typical. |
| Power Dissipation | 0.35 W @ 24 V, typical. |
| Input |
|---|
| Type | 24 Vdc nom (20 to 28.8 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes. |
| Current Consumption | 45 mA @ 24 Vdc, typical. |
| Power Dissipation | 1.1 W @ 24 Vdc, typical. |
| Output |
|---|
| Type | Voltage free 2+2 SPST relay contact (2 paralleled contacts in series) at terminals 7-11 and 8-12, close when relay de-energized, open in energized condition. |
| Contact Material | Ag Alloy (Cd free), gold plated. |
| Contact Rating | 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load). |
| Contact Min. Switching Current | 1 mA. |
| Contact Inrush Current | 6 A @ 24 Vdc, 250 Vac. |
| DC and AC Load Breaking Capacity | Refer to Instruction Manual. |
| Contact Current Derating | Refer to Instruction Manual. |
| Mechanical / Electrical Life | 5 × 10⁶ / 3 × 10⁴ operations, typical. |
| Operate / Release Time | 30 ms / 30 ms, typical. |
| Fault |
|---|
| Type | Load & line short/open circuit, supply voltage monitoring. |
| Line/Load Off OK | 25 Ω ≤ resistance ≤ 19 kΩ, typical. |
| Line/Load Off Fault | Resistance ≤ 15 Ω or ≥ 21 kΩ, typical. |
| Line/Load On OK | 15 mA rms ≤ current ≤ 5 A rms, typical. |
| Line/Load On Fault | Current ≤ 5 mA rms or ≥ 6 A rms, typical. |
| Load Supply Voltage OK | ≥ 20 Vdc/Vac, typical. |
| Load Supply Voltage Fault | ≤ 5 Vdc/Vac, typical. |
| Fault Signalling | Voltage free NE SPST optocoupled open-collector transistor (output de-energized in fault condition). |
| Fault Rating | 100 mA @ 35 Vdc. |
| Fault Output Voltage Drop | < 1 V. |
| Response Time | 0.5 s, typical. |
| Isolation |
|---|
| Test Voltage | Out/In 2.5 kV; Out/Supply 2.5 kV; Out/Fault Out 2.5 kV; In/Supply 500 V; In/Fault Out 500 V; Supply/Fault Out 500 V. |
| Environmental Conditions |
|---|
| Operating Temperature | –40 to +70 °C. |
| Storage Temperature | –45 to +80 °C. |
| Mounting |
|---|
| Type | DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. |
| Weight | About 125 g. |
| Connection | By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
| Dimensions | Width 12.5 mm, Depth 123 mm, Height 120 mm. |