USD USD: TRY
EUR EUR: TRY
GBP GBP: TRY

D5090S-102 SIL3 Relay Out Low-Power 5 A NE Loads

KEY FEATURES

  • 🔹 SIL 3 / SC 3 FOR NE LOADS WITH NE DRIVER
  • 🔹 INSTALLATION IN ZONE 2 / DIV. 2
  • 🔹 UP TO 5 A FUNCTIONAL / 6 A INRUSH CURRENT
  • 🔹 LOAD DISCONNECTION ON BOTH SUPPLY LINES AVAILABLE
  • 🔹 COMPATIBLE WITH DCS / PLC PULSE TESTING
  • 🔹 SERVICE CONTACT AVAILABLE
  • 🔹 INPUT / OUTPUT ISOLATION
🟢 ACTIVE
🔢 CHANNELS: 1
PRODUCT LIFECYCLE POLICY: LEARN MORE

Connections

Dimensions

Certifications

TypeDescriptionAreaNumberIssued byIssue Date
ATEXDEKRA ATEX D5000 Relay Series English Certificate ( EN )EuropeBVS 10 ATEX E 114 XDEKRA2022-04-12
EMCD5000/D6000 EAC EMC Declaration of Conformity ( RU )Eurasian CommunityЕАЭС N RU Д-IT.PA08.B.82326/24CONTROL2024-09-26
ExD5000 CCC certificate for China ( EN )China2020322316000978NEPSI2024-03-22
ExCCOE Indian Approval for D5000 Series ( EN )IndiaP424465PESO2020-07-28
ExEAC Ex Certificate for D5000 Series ( RU )Eurasian CommunityЕАЭС RU С-IT.AA87.В.01310/24CCVE2024-06-13
ExEmirates Certificate of Conformity D5000 ( EN )United Arab Emirates24-05-109026/E24-04-112697/NB0002SGS2024-05-02
ExUL-cUL D5090, D5090-102, D5091, D5091-103 Divisions ( EN )North America20200327-E22230UL2020-04-02
ExINMETRO Certificate DNV 13.0109 X for D5000 ( EN )BrazilDNV 13.0109 XDNV2022-12-10
FSMTUV IT 22 SIL 0093 Functional Safety Certificate ( EN )InternationalTUV IT 22 SIL 0093TUV_SUD2022-07-25
IECExDEKRA IECEx for D5000 Series ( EN )InternationalIECEx BVS 10.0072XDEKRA2022-04-14
SILTUV C-IS-272994-01 SIL Certificate Summary ( EN )InternationalC-IS-272994-01TUV_SUD2022-10-14

Description

Input
Type24 Vdc nom (20 to 28.8 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes.
Current Consumption30 mA @ 24 Vdc, typical.
Power Dissipation0.72 W @ 24 Vdc, typical.
Output
Type1 voltage free SPDT relay contact:
– Out 1 (NO contact): terminals 7-11
– Service Load Out (NC contact): terminals 9-10
1 voltage free SPST relay contact:
– Out 2 (NO contact): terminals 8-12

Terminals 7-11 and 8-12 are open when relay is de-energized, closed when energized.
Service Load output (not SIL) at terminals 9-10 is normally closed when de-energized, open when energized.

Contact MaterialAg Alloy (Cd free), gold plated.
Contact Rating5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load).
Contact Min. Switching Current1 mA.
Contact Inrush Current6 A @ 24 Vdc, 250 Vac.
DC and AC Load Breaking CapacityRefer to Instruction Manual.
Mechanical / Electrical Life5 × 10⁶ / 3 × 10⁴ operations, typical.
Operate / Release Time55 / 30 ms, typical.
Isolation
Test VoltageIn/Outs 2.5 kV; Out 1 / Out 2 500 V.
Environmental Conditions
Operating Temperature–40 to +70 °C.
Storage Temperature–45 to +80 °C.
Mounting
TypeDIN-Rail 35 mm, or on custom Term. Board.
WeightAbout 125 g.
ConnectionBy polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
DimensionsWidth 12.5 mm, Depth 123 mm, Height 120 mm.

Additional information

GMI-Status

Active

GMI-Series

D5000

GMI-Channels

1 N

SIL Seviyesi

SIL 3

GMI-Input-Range

24 Vdc

GMI-Output Type

1 Voltage Free SPDT

LOAD STATUS

NE / Energize To Trip

Max Contact Rating

5 A

Max Load Voltage

250 Vdc

Safety Relay In

Relay Output

GMI-Temperature

-40…+70 °C