D5062S SIL 2 Vibration Transducer Safe Isolator

Key Features

  • 🔹 SIL 3/2 Depending On Applications / SC 3
  • 🔹 Input From Zone 0 / Division 1
  • 🔹 Installation In Zone 2 / Division 2
  • 🔹 Loop Disconnection To Ease Maintenance Operations
  • 🔹 Suitable For AI, AO, DI And DO Applications Without Configuration
  • 🔹 HART® Compatible (Passive And Active AI/AO Loops)
  • 🔹 Line & Load Short/Open Circuit Programmable Diagnostics
  • 🔹 Out-Of-Range Fault With Programmable Thresholds
  • 🔹 Digital Calibration Available Through Configuration Software
  • 🔹 Input And Output Short Circuit Proof
  • 🔹 Field Fault Mirroring To The DCS/PLC UNI Card
  • 🔹 High Accuracy
  • 🔹 Three-Port Isolation, Input/Output/Supply
🟢 Active
Discover Universal – Product Lifecycle Policy

Description

Supply
Voltage24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
Current Consumption90 mA @ 24 Vdc with 20 mA transducer consumption and 2 mA output load, typical.
Power Dissipation2.0 W @ 24 Vdc with 20 mA transducer consumption and 2 mA output load, typical.
Input
Type0 V to -20 V (10 kΩ impedance at terminals 7-8 or 8-9).
3 wires sensor supply voltagemore than -22 V @ 0 mA supply, more than -17 V @ 15 mA supply (current limited @ ≈ 23 mA).
2 wires sensor supply voltagemore than -17 V with constant current supply.
2 wires sensor supply currentselectable @ 4 mA, 6 mA or 10 mA via internal DIP–Switch.
Output
Type0 to -20 V on 10 kΩ load, with 10 Ω output resistance.
Response time≤ 10 µs (10 to 90 % step change).
Frequency responseDC to 20 kHz within 1 dB maximum.
Performance
Ref. Conditions24 V supply, 10 kΩ load, 23 ± 1 °C ambient temperature
Calibration accuracy≤ ± 0.1 % FSR
Linearity accuracy≤ ± 0.05 % FSR
Temp. influence≤ ± 0.005 % on zero/span for a 1 °C change.
Isolation
Test VoltageI.S. In/Out 1.5 kV; I.S. In/Supply 1.5 kV; Out/Supply 500 V
Environmental Conditions
Operating temperaturetemperature limits –40 to +70 °C
Storage temperaturetemperature limits –45 to +80 °C
Safety Description
EquipmentAssociated apparatus and non-sparking electrical equipment
Safety parametersUo = 27 V, Io = 90 mA, Po = 576 mW at terminals 7-8-9-10. Ui = 30 V, Ci = 0 nF, Li = 0 nH at terminals 7-8-9. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C.
Mounting
TypeDIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
Weightabout 125 g.
Connectionby polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm² (13 AWG).
DimensionsWidth 12.5 mm, Depth 123 mm, Height 120 mm.

Additional information

GMI-Applications

Vibration Transducer Input

GMI-Status

Active

SIL Seviyesi

SIL 2

GMI-Temperature

-40…+70 °C