| Type | Description |
|---|---|
| Supply Voltage | 24 Vdc nom (18 to 30 Vdc), reverse polarity protected. |
| Current Consumption | 18 mA @ 24 Vdc with short circuit input and relay energized, typical. |
| Power Dissipation | 0.45 W @ 24 Vdc with short circuit input and relay energized, typical. |
| Input Switching Current Levels | ON ≥ 2.1 mA, OFF ≤ 1.2 mA. |
| Fault Current Levels | open fault ≤ 0.2 mA, short fault ≥ 6.8 mA |
| Input Equivalent Source | 8 V 1 kΩ typical (8 V no load, 8 mA short). |
| Output Type | Voltage free SPDT relay contact. |
| Contact Material | Ag Alloy (Cd free), gold plated. |
| Contact Rating | 4 A 250 Vac 1000 VA, 4 A 250 Vdc 120 W (resistive load). |
| Contact Min. Switching Current | 1 mA. |
| DC and AC Load Breaking Capacity | refer to Instruction Manual. |
| Mechanical / Electrical Life | 5 * 10⁶ / 3 * 10⁴ operation, typical. |
| Operate / Release Time | 8 / 4 ms, typical. |
| Frequency Response | 10 Hz maximum. |
| Isolation Test Voltage | I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; I.S. In/I.S In 500 V; Out/Supply 2.5 kV; Out/Out 2.5 kV. |
| Operating Temperature | temperature limits –40 to +70 °C. |
| Storage Temperature | temperature limits –45 to +80 °C. |
| Safety Description | Associated apparatus and non-sparking electrical equipment. |
| Safety Parameters | Uo = 10.5 V, Io = 22 mA, Po = 56 mW at terminals 7-8, 9-10. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C. |
| Mounting Type | DIN-Rail 35 mm, with or without Power Bus. |
| Weight | about 120 g. |
| Connection | by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
| Dimensions | Width 12.5 mm, Depth 123 mm, Height 120 mm. |
Additional information
| SIL Seviyesi | SIL 3 |
|---|