| Supply Voltage |
24 Vdc nom (18 to 30 Vdc), reverse polarity protected |
| Current Consumption |
90 mA @ 24 Vdc with 20 mA out, typical. |
| Power Dissipation |
1.35 W @ 24 Vdc with 20 mA out, typical. |
| Input Type |
4 to 20 mA (2 wires Tx current limited ≈ 25 mA), reading range 0 to 24 mA. |
| Transmitter Line Voltage |
15.0 V typical, 14.5 V minimum, @ 20 mA. |
| Output Type |
4 to 20 mA, on max. 550 Ω load in source mode (typical 12 V compliance). |
| Response Time |
5 ms (0 to 100 % step change). |
| Performance (Ref. Conditions) |
24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature. |
| Calibration Accuracy |
≤ ± 0.1 % FSR. |
| Linearity Accuracy |
≤ ± 0.05 % FSR. |
| Temperature Influence |
≤ ± 0.01 % FSR on zero/span for a 1 °C change. |
| Isolation Test Voltage |
I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V. |
| Operating Temperature |
–40 to +70 °C |
| Storage Temperature |
–45 to +80 °C |
| Safety Description |
Associated apparatus and non-sparking electrical equipment. |
| Safety Parameters |
Uo = 25.9 V, Io = 92 mA, Po = 594 mW at terminals 7-8, 9-10. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C. |
| Mounting Type |
DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. |
| Weight |
about 140 g |
| Connection |
by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
| Dimensions |
Width 12.5 mm, Depth 123 mm, Height 120 mm. |