| Supply Voltage | 115-230 Vac, 50-60 Hz nom (85 to 250 Vac, 48 to 400 Hz), ripple within voltage limits ≤ 10 Vpp, 500 mA time lag fuse and 275 Vrms transient voltage surge suppressor protected. Limit supply voltage to 250 Vrms for Instrinsic Safety applications. |
| Supply Current consumption @ 115 Vac | 25 mA with short input and relays energized. |
| Supply Current consumption @ 230 Vac | 15 mA with short input and relays energized. |
| Supply Max. power consumption | at 264 Vac supply voltage, short circuit input and relays energized, 2.0 W |
| Input switching current levels Type | ON ≥ 2.1 mA, OFF ≤ 1.2 mA, switch current ≈ 1.65 mA ± 0.2 mA hysteresis. |
| Input switching current levels Fault current levels | open fault ≤ 0.2 mA, short fault ≥ 6.8 mA (when enabled both faults actuate fault relay) |
| Input switching current levels Input equivalent source | 8 V 1 KΩ typical (8 V no load, 8 mA short circuit). |
| Output Type | voltage free SPDT relay contact. |
| Output Contact material | AgCdO. |
| Output Contact rating | 2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). |
| Output DC Load breaking capacity | See Instruction manual |
| Output Mechanical / electrical life | 30 * 10^6 / 1 * 10^5 operation, typical. |
| Output Operate / release time | 7 / 3 ms typical. |
| Output Bounce time NO / NC contact | 3 / 5 ms. |
| Output Response time | 20 ms. |
| Output Frequency response | 10 Hz maximum. |
| Isolation Test Voltage | I.S. In/Out 2.5 KV; I.S. In/Supply 2.5 KV; Out/Supply 2.5 KV; Out/Out 2.5 KV. |
| Isolation Storage | temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. |
| Environmental conditions Operating | temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. |
| Environmental conditions Storage | temperature limits – 45 to + 80 °C. |
| Safety description Safety parameters | Uo/Voc = 10.7 V, Io/Isc = 15 mA, Po/Po = 39 mW at terminals 13-14, 15-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
| Mounting Type | EN/IEC60715 TH 35 DIN-Rail. |
| Mounting Weight | about 145 g |
| Mounting Connection | by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
| Mounting Location | Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
| Mounting Protection class | IP 20 |
| Mounting Dimensions | Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |