USD USD: ⏳ TRY
EUR EUR: ⏳ TRY
GBP GBP: ⏳ TRY

D1052S Analog Signal Converter, Duplicator Subtractor

Ürün Özellikleri

  • 🔹 Zone 0 (Zone 20), Division 1 Girişi, Zone 2, Division 2 Kurulumu
  • 🔹 3 Port İzolasyon: Giriş / Çıkış / Besleme
  • 🔹 EMC Uyumu: EN61000-6-2, EN61000-6-4
  • 🔹 Tam Programlanabilir Çalışma Parametreleri
  • 🔹 ATEX, IECEx, UL & C-UL, FM & FM-C, INMETRO, EAC-EX, UKR TR n.898 Sertifikaları
  • 🔹 DNV ve KR Tip Onay Sertifikası (Denizcilik Uygulamaları)
  • 🔹 Yüksek Yoğunluk: Ünite Başına İki Kanal
  • 🔹 Maks. 250 Vrms (Um) İzin Verilen Gerilim
🔍 Discover D1000
🟡 SPARE-ONLY
Sonraki Aşama: OBSOLETE (31.12.2025)

Description

TypeDescription
Supply Voltage12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
Supply Current Consumption45 mA with 20 mA output typical
Supply Power Dissipation1.0 W with 24 V supply voltage and 20 mA output typical.
Supply Max. power consumptionat 30 V supply voltage, overload condition and PPC1090 connected, 1.4 W
Input Type0/4 to 20 mA (-4 to +24 mA reading) separately powered input, voltage drop ≤ 0.5 V or 0/1 to 5 V or 0/2 to 10 V (-2 to +12 V reading) 1 MΩ impedance.
Input Integration time100 ms.
Input Resolution1 µA on current input, 1 mV on voltage input.
Input Visualization1 µA on current input, 1 mV on voltage input.
Input Input range-4 to +24 mA on current input, -2 to +12 V on voltage input.
Burnout Typeenabled or disabled. Analog output can be programmed to detect burnout condition with downscale or highscale forcing.
Burnout Rangelow and high separated trip point value programmable between -5 to +25 mA on current input and -3 to +13 V on voltage input.
Output Type0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V.
Output Resolution2 µA current output or 1 mV voltage output.
Output Transfer characteristiclinear or reverse.
Output Response time≤ 50 ms (10 to 90 % step change).
Output Output ripple≤ 20 mVrms on 250 Ω load.
Input performance TypeRef. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Input performance Calibration and linearity accuracy≤ ± 20 µA on current input or ≤ ± 10 mV on voltage input.
Input performance Temperature influence≤ ± 2 µA, 1 mV of input for a 1 °C change.
Analog output performance Calibration accuracy≤ ± 0.1 % of full scale.
Analog output performance Linearity error≤ ± 0.05 % of full scale.
Analog output performance Supply voltage influence≤ ± 0.05 % of full scale for a min to max supply change.
Analog output performance Load influence≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change
Analog output performance Temperature influence≤ ± 0.01 % on zero and span for a 1 °C change.
Isolation Test VoltageI.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.
Environmental conditions Operatingtemperature limits -20 to + 60 °C, relative humidity max 95 %.
Environmental conditions Storagetemperature limits -45 to + 80 °C.
Safety description Safety parametersUo/Voc = 10.8 V, Io/Isc = 4 mA, Po/Po = 11 mW at terminals 14-15-16, 10-11-12. Ui/Vmax = 30 V, Ci = 4.5 nF, Li = 0 nH at terminals 14-15-16, 10-11-12. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C.
Mounting TypeEN/IEC60715 TH 35 DIN-Rail.
Mounting Weightabout 140 g
Mounting Connectionby polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Mounting LocationSafe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Mounting Protection classIP 20
Mounting DimensionsWidth 22.5 mm, Depth 99 mm, Height 114.5 mm.

Additional information

GMI-Applications

Analog Input