| Supply Type | 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp |
| Current Consumption | 115 mA @24V with 20 mA output typical |
| Power Dissipation | 1.9 W with 24 V supply voltage and 20 mA output typical |
| Max. Power Consumption | 3.7 W at 30 V supply voltage and short circuit condition |
| Input Type | 0/4 to 20 mA (separately powered input, voltage drop ≤ 0.9 V) or 4 to 20 mA (2 wire Tx current limited at ≈ 25 mA) |
| Transmitter Line Voltage | ≥ 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 40 KHz frequency band |
| Output Type | 0/4 to 20 mA on max. 600 Ω load in source mode; V min. 5 V at 0 Ω load, V max. 30 V in sink mode, current limited at ≈ 23 mA or 0/1 to 5 V on internal 250 Ω shunt (or 0/2 to 10 V on internal 500 Ω shunt on request) |
| Response Time | 50 ms (10 to 90 % step change) |
| Output Ripple | ≤ 20 mVrms on 250 Ω communication load on 0.5 to 40 KHz band |
| Frequency Response | 0.5 to 40 KHz bidirectional within 3 dB (HART® and higher frequency protocols) |
| Ref. Conditions | 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature |
| Calibration Accuracy | ≤ ± 0.1 % of full scale |
| Linearity Error | ≤ ± 0.05 % of full scale |
| Supply Voltage Influence | ≤ ± 0.05 % of full scale for a min to max supply change |
| Load Influence | ≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change |
| Temperature Influence | ≤ ± 0.01 % on zero and span for a 1 °C change |
| Isolation Test Voltage | I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V |
| Safety Description | Associated apparatus and non-sparking electrical equipment |
| Safety Parameters | Uo/Voc = 26.3 V, Io/Isc = 91 mA, Po/Po = 597 mW at terminals 14-15, 10-11; Uo/Voc = 1.1 V, Io/Isc = 38 mA, Po/Po = 11 mW at terminals 15-16, 11-12; Ui/Vmax = 30 V, Ii/Imax = 104 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16, 11-12; Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C |
| Operating Temperature | -20 to +60 °C, relative humidity max 95 % |
| Storage Temperature | -45 to +80 °C |
| Mounting Type | EN/IEC60715 TH 35 DIN-Rail |
| Weight | About 175 g |
| Connection | By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² |
| Location | Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation |
| Protection Class | IP 20 |
| Dimensions | Width 22.5 mm, Depth 99 mm, Height 114.5 mm |