D5091S

The single channel Relay Output, D5091S is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2 for high risk industries. It provides isolation between input and output contacts.
Two mutually exclusive (by DIP-Switch programming) monitoring circuits are provided:
1) line input monitoring, to allow DCS/PLC line monitoring function: when enabled, the module permits a wide compatibility towards different DCS/PLC. Driving line pulse testing, executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering.
2) low voltage input monitoring: when enabled, the module reflects a high impedance state to the control unit when the driving voltage is below the specified threshold.

D5091S provides 1 SPDT contact for two different safety functions:
1) SIL 3 Safety Function for Normally De-Energized load (energized in fail safe state)is available at Terminal Blocks 7-8. The driving signal is normally low (0 Vdc),the relay is normally de-energized, contact is open and load is de-energized. The safety function is met when the driving signal is high (24 Vdc),the relay is energized, contact is closed and load is energized. At Terminal Blocks 9-10 is also available a service contact (for service load) with opposite (not SIL) function.
2) SIL 3 Safety Function for Normally De-Energized load (energized in fail safe state)is available at Terminal Blocks 9-10. The driving signal is normally high (24 Vdc), the relay is normally energized, contact is open and load is de-energized. The safety function is met when the driving signal is low (0 Vdc), the relay is de-energized, contact is closed and load is energized. At Terminal Blocks 7-8 is also available a service contact (for service load) with opposite (not SIL) function.

Mounting on standard DIN-Rail or on customized Termination Boards, in Safe Area / Non Hazardous Location or in Zone 2 / Class I, Division 2 or Class I, Zone 2.

FEATURES

• Systematic capability SIL 3
• Installation in Zone 2 / Division 2.
• 1 SPDT contact for 2 different Safety Functions:
1) SIL 3 for ND load (energized in fail safe state) with ND relay condition (energized in fail safe state)
2) SIL 3 for ND load (energized in fail safe state) with NE relay condition (de-energized in fail safe state)
• Line input monitoring in-field DIP Switch selectable.
• Driving input voltage monitoring.
• Input/Output isolation.
• EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1, EN61326-3-1 for safety system.
• Simplified installation using standard DIN-Rail and plug-in terminal blocks or customized Termination Boards.

Kategoriler:

Ek bilgi

Applications

Safety Relay

Channels

1

Coil Voltage

24 VDC

Contact Material

Gold Plated Ag Alloy

Features

Emerson DeltaV™ alliance

Load Status / Safety Function

ND / De-Energize To Trip, ND / Energize To Trip

Max Contact Rating

5A

Max Load Voltage

250 VAC, 250 VDC

Operating Temperature

-40 / +70 °C

Safety Integrity Level

SIL 3