USD USD: TRY
EUR EUR: TRY
GBP GBP: TRY

D9410S SIL 3 Surge Protective – Voltage Protection

Key Features

  • 🔹 SIL 3 According To IEC 61508:2010
  • 🔹 Input From Zone 0 (Zone 20), Installation In Zone 1 And 2
  • 🔹 Disconnection Of Signal Circuit By Disconnect Knife
  • 🔹 Mechanical Status Indicator Without Auxiliary Power
  • 🔹 High Density – Only 6.2 Mm Per Channel
  • 🔹 HART Compatible
🟢 Active
Discover D9000 – Product Lifecycle Policy

Description

Supply
Nominal System Voltage (Un)24 V DC
Max Continuous Operating Voltage (Uc)30 V DC
Rated Current600 mA (40°C)
Protection
IEC Test ClassificationC1 / C2 / C3 / D1
Protection of Signal Types0/4-20 mA HART, Digital I/O, World FIP, F&G
Nominal Discharge Current (In)(8/20) μs: 5 kA (core-core) / 5 kA (core-ground)
Impulse Discharge Current (Iimp)(10/350) μs: 0.5 kA (core-core) / 0.5 kA (core-ground)
Total Discharge Current (Itotal)(8/20) μs: 10 kA
Max. Total Discharge Current (Imax)(8/20) μs: 20 kA (for one time)
Series Resistance1.65Ω ± 20%
Voltage Protection Level (Up)≤ 55 V (C1 – 1 kV/500 A) core-core
≤ 65 V (C2 – 10 kV/5 kA) core-core
≤ 55 V (C3 – 100 A) core-core
≤ 900 V (C1 – 1 kV/500 A) core-ground
≤ 1.05 kV (C2 – 10 kV/5 kA) core-ground
≤ 1.4 kV (C3 – 100 A) core-ground
Response Time (tA)≤ 1 ns (core-core), ≤ 100 ns (core-ground)
Environmental Conditions
Operating TemperatureTemperature limits –40 to +85 °C, relative humidity 5% to 95%.
Mounting
TypeEN/IEC60715 TH 35 DIN-Rail.
WeightAbout 37 g.
ConnectionScrew terminal blocks to accommodate terminations up to 2.5 mm² flexible.
LocationInstallation in Safe Area or Zone 2 or Zone 1, Group IIC T4…T6.
Protection ClassIP20.
DimensionsWidth 6.2 mm, Depth 83.5 mm, Height 105.8 mm.

Additional information

GMI Surge Arresters

Surge Protective Device Remote Signaling

GMI-Status

Active

GMI-Series

D9000

SIL Seviyesi

SIL 3

GMI-Features

HART© Compatible

Max Load Voltage

24 Vdc

GMI-Temperature

40…+85 °C