| Input |
|---|
| Voltage | 24 Vdc nom (20.4 to 27.6 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
| Current Consumption | 50 mA for each channel with relay energized, typical (100 mA for 2 channels D1092D-069 when used as duplicator 1 input / 2 outputs). |
| Power Dissipation | 1.2 W for each channel with 24 V input voltage and relay energized, typical (2.4 W for 2 channels D1092D-069 when used as duplicator). |
| Max. Power Consumption | At 27.6 V input voltage and relay energized, 1.5 W for each channel (3.0 W for 2 channels D1092D-069 when used as duplicator). |
| Output |
|---|
| Type | Voltage free SPST NO+SPST NC relay contact. |
| Contact Material | Ag Alloy (Cd free). |
| Contact Rating | 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load). |
| Contact Inrush Current | 5 A at 30 Vdc, 250 Vac. |
| Contact Min. Switching Current | 10 mA. |
| DC Load Breaking Capacity | See instruction Manual. |
| Mechanical / Electrical Life | 50 × 10⁶ / 1 × 10⁵ operations, typical. |
| Operate / Release Time | 5 / 3 ms typical. |
| Bounce Time NO / NC Contact | 3 ms. |
| Frequency Response | 10 Hz maximum. |
| Isolation |
|---|
| Test Voltage | Input/Output 2.5 KV; Input/Input 500 V; Output/Output 2.5 KV; Output A/Output B 1.5 KV. |
| Environmental Conditions |
|---|
| Operating | Temperature limits -20 to +60 °C, relative humidity max 95%. |
| Storage | Temperature limits -45 to +80 °C. |
| Mounting |
|---|
| Type | EN/IEC60715 TH 35 DIN-Rail. |
| Weight | About 145 g. |
| Connection | By polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm². |
| Location | Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
| Protection Class | IP 20. |
| Dimensions | Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |