D5293S SIL3 Relay Out Module 5 A NE Loads LFD

Key Features

  • 🔹 SIL 3 / SC 3 For NE Loads With NE Driver
  • 🔹 SIL 2 / SC 3 For Fault Outputs
  • 🔹 Installation In Zone 2 / Division 2
  • 🔹 Up To 5 A Functional / 6 A Inrush Current
  • 🔹 Load Disconnection On Both Supply Lines Available
  • 🔹 Compatible With DCS / PLC Pulse Testing
  • 🔹 Line & Load Short/Open Circuit Detection
  • 🔹 Load Voltage Monitoring
  • 🔹 Field Fault Mirroring To The PLC DO
  • 🔹 Modbus RTU RS-485 For Monitor & Configuration
  • 🔹 Service Contact Available
  • 🔹 Input / Output / Supply Isolation
🟢 Active
🔢 Channels: 1
Product Lifecycle Policy: Details

Description

Supply
Type24 Vdc nom (18 to 30 Vdc), reverse polarity protected.
Current Consumption40 mA @ 24 V (no fault), typical.
Power Dissipation1.0 W @ 24 V (no fault), typical.
Input
Type24 Vdc nom (21.6 to 27.6 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes.
Current Consumption40 mA @ 24 Vdc (no fault), typical.
Power Dissipation1.0 W @ 24 Vdc (no fault), typical.
Output
TypeVoltage free 1 + 1 SPST relay contact at terminals 13-15 and 14-16, opens when relay is de-energized (fail safe state), close in energized condition.
Contact MaterialAg Alloy (Cd free), gold plated.
Contact Rating5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load).
Contact Min. Switching Current1 mA.
Contact Inrush Current6 A @ 24 Vdc, 250 Vac.
DC and AC Load Breaking CapacityRefer to Instruction Manual.
Contact Current DeratingRefer to Instruction Manual.
Mechanical / Electrical Life5 × 10⁶ / 3 × 10⁴ operations, typical.
Operate / Release Time30 ms / 30 ms, typical.
Fault
TypeLoad & line short/open circuit, supply voltage monitoring.
Line + Load ResistanceProgrammable up to 50 kΩ.
Load CurrentProgrammable up to 5 A.
Load Supply VoltageProgrammable up to 250 Vdc/Vac.
Fault SignalingVoltage free DPST contact.
Fault 1 Rating0.5 A 30 Vac 15 VA, 0.5 A 50 Vdc 25 W (resistive load).
Fault 2 Rating3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load).
Response Time4 s, typical.
Modbus Interface
TypeModbus RTU RS-485 up to 115.2 kbps for monitor/configuration/control.
Isolation
Test VoltageOut/In 2.5 kV; Out/Supply 2.5 kV; Out/Fault Outs 2.5 kV; Out/RS485 Modbus 2.5 kV; In/Supply 500 V; In/Fault Out 1 500 V; In/Fault Out 2 2.5 kV; In/RS485 Modbus 500 V; Supply/Fault Out 1 500 V; Supply/Fault Out 2 2.5 kV; Supply/RS485 Modbus 500 V.
Environmental Conditions
Operating Temperature–40 to +70 °C.
Storage Temperature–45 to +80 °C.
Mounting
TypeDIN-Rail 35 mm, with or without Power Bus or on custom Term. Board.
WeightAbout 230 g.
ConnectionBy polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG).
DimensionsWidth 22.5 mm, Depth 123 mm, Height 120 mm.

Additional information

GMI-Status

Active

GMI-Series

D5000

GMI-Channels

1 N

SIL Seviyesi

SIL 3

GMI-Input-Range

24 Vdc

GMI-Output Type

1 Voltage Free SPDT

LOAD STATUS

NE / Energize To Trip

Max Contact Rating

5 A

Max Load Voltage

250 Vdc

Safety Relay In

Relay Output

GMI-Temperature

-40…+70 °C