D5090S-103 SIL3 Relay Out Low-Power 5 A NE Loads
Key Features
- 🔹 SIL 3 / SC 3 For ND / F&G Loads With ND / NE Driver
- 🔹 Installation In Zone 2 / Div. 2
- 🔹 Up To 5 A Functional / 6 A Inrush Current
- 🔹 Low Current Consumption
- 🔹 Service Contact Available
- 🔹 Input / Output Isolation
Dimensions
Certifications
| Type | Description | Area | Number | Issued by | Issue Date |
|---|---|---|---|---|---|
| ATEX | DEKRA ATEX D5000 Relay Series English Certificate ( EN ) | Europe | BVS 10 ATEX E 114 X | DEKRA | 2022-04-12 |
| EMC | D5000/D6000 EAC EMC Declaration of Conformity ( RU ) | Eurasian Community | ЕАЭС N RU Д-IT.PA08.B.82326/24 | CONTROL | 2024-09-26 |
| Ex | D5000 CCC certificate for China ( EN ) | China | 2020322316000978 | NEPSI | 2024-03-22 |
| Ex | CCOE Indian Approval for D5000 Series ( EN ) | India | P424465 | PESO | 2020-07-28 |
| Ex | EAC Ex Certificate for D5000 Series ( RU ) | Eurasian Community | ЕАЭС RU С-IT.AA87.В.01310/24 | CCVE | 2024-06-13 |
| Ex | Emirates Certificate of Conformity D5000 ( EN ) | United Arab Emirates | 24-05-109026/E24-04-112697/NB0002 | SGS | 2024-05-02 |
| Ex | UL-cUL D5090, D5090-102, D5091, D5091-103 Divisions ( EN ) | North America | 20200327-E22230 | UL | 2020-04-02 |
| Ex | INMETRO Certificate DNV 13.0109 X for D5000 ( EN ) | Brazil | DNV 13.0109 X | DNV | 2022-12-10 |
| FSM | TUV IT 22 SIL 0093 Functional Safety Certificate ( EN ) | International | TUV IT 22 SIL 0093 | TUV_SUD | 2022-07-25 |
| IECEx | DEKRA IECEx for D5000 Series ( EN ) | International | IECEx BVS 10.0072X | DEKRA | 2022-04-14 |
| SIL | TUV C-IS-272994-01 SIL Certificate Summary ( EN ) | International | C-IS-272994-01 | TUV_SUD | 2022-10-14 |
Description
| Input | |
|---|---|
| Type | 24 Vdc nom (20 to 28.8 Vdc), reverse polarity protected. Relay coils are internally protected with suppressor diodes. |
| Current Consumption | 30 mA @ 24 Vdc, typical. |
| Power Dissipation | 0.72 W @ 24 Vdc, typical. |
| Output | |
| Type | 1 voltage free SPDT relay contact: – Out 1 (NO contact): terminals 7-11 – Service Load Out (NC contact): terminals 9-10 1 voltage free SPST relay contact: – Out 2 (NO contact): terminals 8-12Terminals 7-11 and 8-12 are open when relay is de-energized, closed when energized. Service Load output (not SIL) at terminals 9-10 is normally closed when de-energized, open when energized. |
| Contact Material | Ag Alloy (Cd free), gold plated. |
| Contact Rating | 5 A 250 Vac 1250 VA, 5 A 250 Vdc 140 W (resistive load). |
| Contact Min. Switching Current | 1 mA. |
| Contact Inrush Current | 6 A @ 24 Vdc, 250 Vac. |
| DC and AC Load Breaking Capacity | Refer to Instruction Manual. |
| Mechanical / Electrical Life | 5 × 10⁶ / 3 × 10⁴ operations, typical. |
| Operate / Release Time | 55 / 30 ms, typical. |
| Isolation | |
| Test Voltage | In/Outs 2.5 kV; Out 1 / Out 2 500 V. |
| Environmental Conditions | |
| Operating Temperature | –40 to +70 °C. |
| Storage Temperature | –45 to +80 °C. |
| Mounting | |
| Type | DIN-Rail 35 mm, or on custom Term. Board. |
| Weight | About 125 g. |
| Connection | By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
| Dimensions | Width 12.5 mm, Depth 123 mm, Height 120 mm. |
Additional information
| GMI-Status | Active |
|---|---|
| GMI-Series | D5000 |
| GMI-Channels | 1 N |
| SIL Seviyesi | SIL 3 |
| GMI-Input-Range | 24 Vdc |
| GMI-Output Type | 1 Voltage Free SPDT |
| LOAD STATUS | NE / Energize To Trip |
| Max Contact Rating | 5 A |
| Max Load Voltage | 250 Vdc |
| Safety Relay In | Relay Output |
| GMI-Temperature | -40…+70 °C |