D5264S SIL2 Load Cell Strain Gauge Bridge Repeater
D5264S SIL2 Load Cell Strain Gauge Bridge Repeater
Connections
Description
| Type | Description |
|---|---|
| Supply Voltage | 24 Vdc nom (18 to 30 Vdc), reverse polarity protected. |
| Current Consumption | 75 mA @ 24 Vdc with four 350 Ω load cells connected, typical. |
| Power Dissipation | 1.8 W @ 24 Vdc with four 350 Ω load cells connected, typical. |
| Input Type | Up to four 350 Ω load cells in parallel or up to five 450 Ω or ten 1000 Ω in parallel. |
| Integration Time | 12.5 ms. |
| Bridge Supply Voltage | 4.0 Vdc nominal. |
| Bridge Output Signal | 1 to 4 mV/V. |
| Output Type | Same as the input signal. |
| Output Impedance | 500 Ω, typical. |
| Excitation Voltage | Externally applied between 4 V and 15 V. |
| Transfer Characteristic | Linear. |
| Response Time | ≤ 20 ms (10 to 90 % step change). |
| Calibration Accuracy | ≤ ± 0.003 % input FSR, after system calibration. |
| Linearity Accuracy | ≤ ± 0.002 % input FSR. |
| Temp. Influence | ≤ ± 0.002 % input FSR for a 1 °C change. |
| Isolation Test Voltage | I.S. In/Out 2.5 kV; I.S. In/Supply 2.5 kV; Out/Supply 500 V. |
| Operating Temperature | –40 to +70 °C. |
| Storage Temperature | –45 to +80 °C. |
| Safety Description | Associated apparatus and non-sparking electrical equipment. |
| Safety Parameters | Uo = 7.2 V, Io = 177 mA, Po = 471 mW at terminals 13-14-15-16-17-18. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70°C. |
| Mounting Type | DIN-Rail 35 mm, with or without Power Bus. |
| Weight | About 165 g. |
| Connection | By polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
| Dimensions | Width 22.5 mm, Depth 123 mm, Height 120 mm. |
Additional information
| SIL Seviyesi | SIL 2 |
|---|