USD USD: ⏳ TRY
EUR EUR: ⏳ TRY
GBP GBP: ⏳ TRY

D2052M Safe Relay Output Multiplexer DIN RAIL

Key Features

  • 🔹 Output Repeater For D2030M Digital Multiplexer
  • 🔹 SPDT Relay Output Signals
  • 🔹 High Density – 32 Channels Per Unit, 128 Per System
  • 🔹 EMC Compatibility: EN61000-6-2, EN61000-6-4
  • 🔹 Discover D2000 Series
🟢 Active
32 Channels – Product Lifecycle Policy

Description

Supply
VoltageVia D2050M gateway unit.
Max. Power Consumption200 mW.
Input
Switching Current LevelsON ≥ 2.1 mA, OFF ≤ 1.2 mA, switch current ≈ 1.65 mA ± 0.2 mA hysteresis.
Fault Current LevelsOpen fault ≤ 0.2 mA, short fault ≥ 6.0 mA.
Fault DetectionEnabled or disabled, programmable independently for each channel.
Input Equivalent Source7.5 V 1 KΩ typical (7.5 V no load, 7.5 mA short circuit).
Input Channels32.
Excitation TimeProgrammable from 1 ms to 35 ms independently for each channel.
Scan Cycle Time50 ms for four D2030M units (128 channels) at minimum sensor excitation time or the sum of each channel scan time, whichever is greater.
Isolation
Test VoltageI.S. In/Supply-Communication line 500 V; I.S. In/Ground 500 V; I.S. In/I.S. In between units 500 V; Communication line/Ground 500 V.
Environmental Conditions
OperatingTemperature limits –40 to +60 °C, relative humidity max 90 % non-condensing, up to 35 °C.
StorageTemperature limits –45 to +80 °C.
Safety Description
Safety ParametersUo/Voc = 10.7 V, Io/Isc = 14 mA, Po/Po = 38 mW at terminals 1-2, 3-4 of channel 1 to 32. -40 °C ≤ Ta ≤ 60 °C.
Mounting
TypeT35 DIN Rail according to EN50022.
WeightAbout 680 g.
ConnectionBy polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
LocationSafe Area/Non Hazardous Locations or Zone 1, 2, Group IIC, IIB, IIA T4, Class I, Division 1, Groups A, B, C, D Temperature Code T4 and Class I, Zone 1, 2, Group IIC, IIB, IIA T4 installation.
Protection ClassIP 20.
DimensionsWidth 127 mm, Length 220 mm, Depth 78 mm.

Additional information

GMI-Status

Active

GMI-Channels

32 N.

Multiplexer Systems

Intrinsically Safe Multiplexer System

GMI-Temperature

-40…+60 °C