USD USD: ⏳ TRY
EUR EUR: ⏳ TRY
GBP GBP: ⏳ TRY

D1046Y Digital Output Bus Powered Isolator

Ürün Özellikleri

  • 🔹 Zone 0 (Zone 20), Division 1 Giriş – Zone 2, Division 2 Kurulum
  • 🔹 İzole Komutlarla Gerilim Girişi, Loop Powered veya Bus Powered
  • 🔹 1 veya 2 Pozisyonlu Yön Kontrol Valflerini Sürmek İçin Uygun
  • 🔹 Çıkış Kısa Devre Korumalı ve Akım Sınırlamalı
  • 🔹 Üç Port İzolasyonu: Giriş / Çıkış / Besleme
  • 🔹 EMC Uyumluluğu: EN61000-6-2, EN61000-6-4
  • 🔹 Maks. 250 Vrms (Um) İzin Verilen Gerilim
🟢 ACTIVE

Description

TypeDescription
Supply Voltage24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
Supply Current Consumption130 mA with four channels energized at nominal load, 150 mA with short circuit output
Supply Power Dissipation2.3 W with 24 V supply voltage and four channels energized at nominal load.
Supply Max. power consumptionat 30 V supply voltage and short circuit output, 4.0 W
Input Typeswitch contact, logic level common positive or common negative or loop powered.
Input Trip voltage levelsOFF status ≤ 1.0 V, ON status ≥ 6.0 V (maximum 30 V).
Input Current Consumption3 Ma @24V (≈ 10 KΩ input impedance).
Output Type22 mA at 13.2 V per channel (20.5 V no load, 334 Ω series resistance).
Output Short circuit current≥ 24 mA per channel (26 mA typical)
Output Response time20 ms (power up in 600 ms typical in loop powered mode).
Isolation Test VoltageI.S. Out/In 1.5 KV; I.S. Out/Supply 1.5 KV; In/Supply 500 V.
Environmental conditions Operatingtemperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C.
Environmental conditions Storagetemperature limits -45 to + 80 °C.
Safety description Safety parametersUo/Voc = 23.6 V, Io/Isc = 72 mA, Po/Po = 424 mW at terminals 13-14,15-16,9-10,11-12.
Mounting TypeEN/IEC60715 TH 35 DIN-Rail.
Mounting Weightabout 130 g.
Mounting Connectionby polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2.
Mounting LocationSafe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Mounting Protection classIP 20.
Mounting DimensionsWidth 22.5 mm, Depth 99 mm, Height 114.5 mm.

Additional information

GMI-Applications

Digital Output

SIL Seviyesi

SIL 2