USD USD: TRY
EUR EUR: TRY
GBP GBP: TRY

D1010D-046 SIL 2 Power Supply Compatible DIN-Rail

Ürün Özellikleri

  • 🔹 SIL2 / SC3 Uyumlu
  • 🔹 Zone 0 / Zone 20 Giriş, Zone 2 Kurulum
  • 🔹 4–20 mA veya 0–20 mA Giriş / Çıkış Sinyali
  • 🔹 HART® Uyumlu Geniş Bant İletişim
  • 🔹 Kısa Devre Korumalı Giriş ve Çıkış
  • 🔹 Yüksek Doğruluk & Üç Port İzolasyon (Giriş/Çıkış/Besleme)
  • 🔹 DIP Switch ile Sahada Programlanabilir
  • 🔹 250 Vrms Maksimum Gerilim Toleransı
🟡 PHASE-OUT
YEDEK PARÇA TEDARIK: 01.01.2027 Kadar.

Description

TypeDescription
Supply Type24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp.
Current Consumption115 mA @24V with 20 mA output typical.
Power Dissipation1.9 W with 24 V supply voltage and 20 mA output typical.
Max. Power Consumption3.7 W at 30 V supply voltage and short circuit condition
Input Type0/4 to 20 mA (separately powered input, voltage drop ≤ 0.9 V) or 4 to 20 mA (2 wire Tx current limited at ≈ 25 mA).
Transmitter Line Voltage≥ 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 40 KHz frequency band.
Output Type0/4 to 20 mA, on max. 600 Ω load in source mode; V min. 5 V at 0 Ω load, V max. 30 V in sink mode, current limited at ≈ 23 mA or 0/1 to 5 V on internal 250 Ω shunt (or 0/2 to 10 V on internal 500 Ω shunt on request).
Response Time50 ms (10 to 90 % step change).
Output Ripple≤ 20 mVrms on 250 Ω communication load on 0.5 to 40 KHz band.
Frequency Response0.5 to 40 KHz bidirectional within 3 dB (HART® and higher frequency protocols).
Ref. Conditions24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature.
Calibration Accuracy≤ ± 0.1 % of full scale.
Linearity Error≤ ± 0.05 % of full scale.
Supply Voltage Influence≤ ± 0.05 % of full scale for a min to max supply change.
Load Influence≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change.
Temperature Influence≤ ± 0.01 % on zero and span for a 1 °C change.
Isolation Test VoltageI.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V.
Safety DescriptionAssociated apparatus and non-sparking electrical equipment
Safety ParametersUo/Voc = 26.3 V, Io/Isc = 91 mA, Po/Po = 597 mW at terminals 14-15, 10-11; Uo/Voc = 1.1 V, Io/Isc = 38 mA, Po/Po = 11 mW at terminals 15-16, 11-12; Ui/Vmax = 30 V, Ii/Imax = 104 mA, Ci = 1.05 nF, Li = 0 nH at terminals 15-16, 11-12; Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C.
Operating TemperatureTemperature limits -20 to + 60 °C, relative humidity max 95 %.
Storage TemperatureTemperature limits -45 to + 80 °C.
Mounting TypeEN/IEC60715 TH 35 DIN-Rail.
WeightAbout 175 g
ConnectionBy polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm².
LocationSafe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Protection ClassIP 20.
DimensionsWidth 22.5 mm, Depth 99 mm, Height 114.5 mm

Additional information

GMI-Applications

Analog Input

GMI-Series

D1000

SIL Seviyesi

SIL 2

GMI-Temperature

-20…+60 °C

Max Load Voltage

24 Vdc

GMI-Status

Phase Out