| Supply |
| Voltage |
24 Vdc nom (18 to 30 Vdc) reverse polarity protected, provided through Termination Board. |
| Current Consumption |
20 mA @ 24 Vdc typical (modem only), 40 mA @ 24 Vdc in full topology (with maximum number of extension boards), typical. |
| Power Dissipation |
0.5 W @ 24 Vdc typical (modem only), 1 W @ 24 Vdc in full topology (with maximum number of extension boards), typical. |
| Field Interface |
| Number of Channels |
256. |
| HART® Field Device Revision |
5 to 7. |
| Write Protection |
| Type |
The HART® Multiplexer Modem 5700 can be protected against writing by shorting terminals 7 and 8. |
| Serial Interface |
| Type |
RS-485 differential pair and grounding. |
| Topology |
Multi-drop, master/slave connection. |
| Address |
0 – 62, software configurable. |
| Baud Rate |
From 1200 to 115200 bps, software configurable. |
| Isolation |
| Type |
Field Interface/Serial Interface 500 V; Field Interface/Supply 500 V; Supply/Serial Interface 500 V. |
| Environmental Conditions |
| Operating Temperature |
–40 to +70 °C. |
| Max Altitude |
2000 m a.s.l. |
| Storage Temperature |
–45 to +80 °C. |
| Mounting |
| Type |
On custom Term. Board. |
| Weight |
About 100 g. |
| Location |
Installation in Safe Area or Zone 2, Group IIC T4, or Class 1, Div. 2, Group A, B, C, D, T4. |
| Connection |
Width 235 mm, Depth 135 mm, Height 154 mm. |
| Dimensions |
Width 12.5 mm, Depth 123 mm, Height 120 mm. |